Plan Review Notes
Plan Review Notes For Permit 19071220
Permit Number 19071220
Review Stop G
Sequence Number 1
Notes
Date Text
2019-07-30 11:11:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 GAS COMMENTS
 1. RE: MASTER PERMIT #18080814, PLAN SHEET A-1 PROPOSED
 FLOOR PLAN INDICATES A GENERATOR BY OWNER AS WELL AS A
 GAS TANKLESS WATER HEATER INSIDE OF THE BUILDING. PLAN
 SHEET E-1 SHOWS ON THE ELECTRICAL FLOOR PLAN INDICATES
 THE GENERATOR IS INSTALLED UNDER A SEPARATE PERMIT.
 (SEE 19020275 FOR GENERATOR AND WATER HEATER 2/6/2019).
 THE GENERATOR AS SHOWN ON THE SUBMITTED GAS PLAN IS NOT
 LOCATED AS SHOWN ON A-1 AND E-1. PER FBC WPB 107.2.1,
 RECONCILE ALL PLANS WITH EACH OTHER, AND SHOW LOCATION
 OF GENERATOR ON SP-1 SITE PLAN. SHOW DISTANCE FROM
 GENERATOR EXHAUST TO NEAREST VENTILATING OPENING
 (WINDOW, LOUVER, ETC.)
  
 2. A SEARCH OF PAST RECORDS INDICATES THAT UNDER A
 PREVIOUS PERMIT #03051323 DATED 5/16/2003, A NATURAL
 GAS SYSTEM WAS PREVIOUSLY INSTALLED FOR GAS NATURAL GAS
 FROM THE METER TO POOL HEATER, RANGE AND FUTURE BBQ.
 THE SYSTEM LENGTH WAS 145? AND THE DEMAND WAS 530 MBTU.
 PER WPB FBC 107.2.1, PLEASE SHOW THE RELATIONSHIP OF
 THE NEW SYSTEM TO THE EXISTING AND AS IT APPEARS THAT
 THIS WOULD BE AN ADDITION TO THE ORIGINAL SYSTEM,
 PLEASE REVISE SIZING BASED ON THE LONGEST LENGTH AS
 NOTED IN FBC FG TABLE 402.4(21) WHICH AS I SEE IT WOULD
 BE 150?, NOT 60?. SUBMIT THE REVISED RISER DIAGRAM AND
 PIPING LAYOUT ON PLAN SHEET SP-1. PLAN TO BE PROVIDED
 WITH NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN PER WPB FBC 107.2.1. PER WPB FBC 107.2.1,
 NOTE ON THE PLAN THE APPLICABLE INFORMATION REQUIRED TO
 INCLUDE BUT NOT NECESSARILY LIMITED TO
  
 A.GAS TYPE
 B.PRESSURE
 C. LENGTH FROM METER TO FARTHEST POINT
 D. TABLES USED FOR SIZING
 E.APPLIANCE LIST WITH BTUS
 F. TOTAL BTUS OF NEW SYSTEM
 G. TOTAL BTUS OF EXISTING SYSTEM
  
  
 3. SHOW TRANSITION FROM UNDERGROUND POLY PIPE TO
 ABOVEGROUND PIPING AND SPECIFY MATERIAL TYPE AND SIZE.
 PROVIDE TABLE FOR SIZING OF SAID MATERIAL.
  
 4. PROVIDE A DETAIL OF COMBUSTION AIR AND EXHAUST VENTS
 TO THE EXTERIOR AND PROVIDE LOCATION AND ELEVATION FOR
 THE VENTS ON TO COMPLY WITH FBC FG SECTIONS 502 THROUGH
 505/FBC RES SECTIONS G2426 THROUGH G2439.
  
 5. RESUBMIT EQUIPMENT SPECS SUBMITTED WITH PERMIT
 #19020275, VOID THE OUTDOOR MODEL PAGE (MANUFACTURER?S
 PAGE 4 OF 6) (TITON BUILDER?S FAX PAGE 005/007)
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  