| Date |
Text |
| 2019-07-30 11:11:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS |
| | 1. RE: MASTER PERMIT #18080814, PLAN SHEET A-1 PROPOSED |
| | FLOOR PLAN INDICATES A GENERATOR BY OWNER AS WELL AS A |
| | GAS TANKLESS WATER HEATER INSIDE OF THE BUILDING. PLAN |
| | SHEET E-1 SHOWS ON THE ELECTRICAL FLOOR PLAN INDICATES |
| | THE GENERATOR IS INSTALLED UNDER A SEPARATE PERMIT. |
| | (SEE 19020275 FOR GENERATOR AND WATER HEATER 2/6/2019). |
| | THE GENERATOR AS SHOWN ON THE SUBMITTED GAS PLAN IS NOT |
| | LOCATED AS SHOWN ON A-1 AND E-1. PER FBC WPB 107.2.1, |
| | RECONCILE ALL PLANS WITH EACH OTHER, AND SHOW LOCATION |
| | OF GENERATOR ON SP-1 SITE PLAN. SHOW DISTANCE FROM |
| | GENERATOR EXHAUST TO NEAREST VENTILATING OPENING |
| | (WINDOW, LOUVER, ETC.) |
| | |
| | 2. A SEARCH OF PAST RECORDS INDICATES THAT UNDER A |
| | PREVIOUS PERMIT #03051323 DATED 5/16/2003, A NATURAL |
| | GAS SYSTEM WAS PREVIOUSLY INSTALLED FOR GAS NATURAL GAS |
| | FROM THE METER TO POOL HEATER, RANGE AND FUTURE BBQ. |
| | THE SYSTEM LENGTH WAS 145? AND THE DEMAND WAS 530 MBTU. |
| | PER WPB FBC 107.2.1, PLEASE SHOW THE RELATIONSHIP OF |
| | THE NEW SYSTEM TO THE EXISTING AND AS IT APPEARS THAT |
| | THIS WOULD BE AN ADDITION TO THE ORIGINAL SYSTEM, |
| | PLEASE REVISE SIZING BASED ON THE LONGEST LENGTH AS |
| | NOTED IN FBC FG TABLE 402.4(21) WHICH AS I SEE IT WOULD |
| | BE 150?, NOT 60?. SUBMIT THE REVISED RISER DIAGRAM AND |
| | PIPING LAYOUT ON PLAN SHEET SP-1. PLAN TO BE PROVIDED |
| | WITH NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN PER WPB FBC 107.2.1. PER WPB FBC 107.2.1, |
| | NOTE ON THE PLAN THE APPLICABLE INFORMATION REQUIRED TO |
| | INCLUDE BUT NOT NECESSARILY LIMITED TO |
| | |
| | A.GAS TYPE |
| | B.PRESSURE |
| | C. LENGTH FROM METER TO FARTHEST POINT |
| | D. TABLES USED FOR SIZING |
| | E.APPLIANCE LIST WITH BTUS |
| | F. TOTAL BTUS OF NEW SYSTEM |
| | G. TOTAL BTUS OF EXISTING SYSTEM |
| | |
| | |
| | 3. SHOW TRANSITION FROM UNDERGROUND POLY PIPE TO |
| | ABOVEGROUND PIPING AND SPECIFY MATERIAL TYPE AND SIZE. |
| | PROVIDE TABLE FOR SIZING OF SAID MATERIAL. |
| | |
| | 4. PROVIDE A DETAIL OF COMBUSTION AIR AND EXHAUST VENTS |
| | TO THE EXTERIOR AND PROVIDE LOCATION AND ELEVATION FOR |
| | THE VENTS ON TO COMPLY WITH FBC FG SECTIONS 502 THROUGH |
| | 505/FBC RES SECTIONS G2426 THROUGH G2439. |
| | |
| | 5. RESUBMIT EQUIPMENT SPECS SUBMITTED WITH PERMIT |
| | #19020275, VOID THE OUTDOOR MODEL PAGE (MANUFACTURER?S |
| | PAGE 4 OF 6) (TITON BUILDER?S FAX PAGE 005/007) |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19071220 210 VALENCIA RD |
| | |
| | |
| | MASTER PERMIT 18080814/19020275 |