| 2019-08-01 07:04:24 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. $5000 VALUE FOR AMOUNT OF WORK SHOWN IS NOT |
| | POSSIBLE. RAISE VALUE OR VALUE WILL BE SET BY BUILDING |
| | OFFICIAL. VALUE TO INCLUDE ALL MATERIALS AND LABOR |
| | (INCLUDE GENERATOR) PER |
| | |
| | FBC 109.3 |
| | BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2. PROVIDE CUT SHEETS OF ALL EQUIPMENT FOR PRODUCT |
| | APPROVAL TO INCLUDE GENERATOR. FBC 107.2.1, NEC 90.7, |
| | 110.2, 110.3B |
| | |
| | 3. ONE-LINE DIAGRAM SHOWS 3-3/0 AND 1- #4 EQUIPMENT |
| | GROUND FROM METER-CAN TO SERVICE DISCONNECT, EQUIPMENT |
| | GROUND FROM METER-CAN TO SERVICE DISCONNECT IS NOT |
| | PERMITTED. EQUIPMENT GROUND ORIGINATES AT SERVICE |
| | DISCONNECTING MEANS. NEC 250.130A |
| | |
| | 4. GROUNDING ELECTRODE SYSTEM IS SHOWN MAKING ITS |
| | ATTACHMENT TO THE GROUNDED CONDUCTOR (NEUTRAL) IN THE |
| | ATS WHICH IS DOWN STREAM FROM BOTH THE METER-CAN AND |
| | SERVICE DISCONNECTING MEANS, ATTACHMENT OF GROUNDING |
| | ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR IS NOT |
| | PERMITTED AFTER THE SERVICE DISCONNECTING MEANS. |
| | PROVIDE CORRECTION. NEC 250.24A1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |