Plan Review Notes
Plan Review Notes For Permit 19071219
Permit Number 19071219
Review Stop E
Sequence Number 1
Notes
Date Text
2019-08-01 07:04:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. $5000 VALUE FOR AMOUNT OF WORK SHOWN IS NOT
 POSSIBLE. RAISE VALUE OR VALUE WILL BE SET BY BUILDING
 OFFICIAL. VALUE TO INCLUDE ALL MATERIALS AND LABOR
 (INCLUDE GENERATOR) PER
  
 FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2. PROVIDE CUT SHEETS OF ALL EQUIPMENT FOR PRODUCT
 APPROVAL TO INCLUDE GENERATOR. FBC 107.2.1, NEC 90.7,
 110.2, 110.3B
  
 3. ONE-LINE DIAGRAM SHOWS 3-3/0 AND 1- #4 EQUIPMENT
 GROUND FROM METER-CAN TO SERVICE DISCONNECT, EQUIPMENT
 GROUND FROM METER-CAN TO SERVICE DISCONNECT IS NOT
 PERMITTED. EQUIPMENT GROUND ORIGINATES AT SERVICE
 DISCONNECTING MEANS. NEC 250.130A
  
 4. GROUNDING ELECTRODE SYSTEM IS SHOWN MAKING ITS
 ATTACHMENT TO THE GROUNDED CONDUCTOR (NEUTRAL) IN THE
 ATS WHICH IS DOWN STREAM FROM BOTH THE METER-CAN AND
 SERVICE DISCONNECTING MEANS, ATTACHMENT OF GROUNDING
 ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR IS NOT
 PERMITTED AFTER THE SERVICE DISCONNECTING MEANS.
 PROVIDE CORRECTION. NEC 250.24A1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  