2019-08-23 18:36:13BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-BASED ON PLANS SUBMITTED THE SCOPE OF WORK IS NOT A
 LEVEL 1 ALTERATION. THIS IS A CHANGE OF OCCUPANCY (SEC.
 506 FBC-EXISTING BUILDING) AND ALTERATION LEVEL 2 (SEC.
 506 FBC-EXISTING BUILDING). PLANS SHOW EXISTING
 CLASSROOMS AND OFFICE SPACES TO BE CONVERTED TO A
 DIFFERENT USE. REVISE CODE INFORMATION ON SHEET A0.0.
  
 2- ARCHITECT NEEDS TO SPECIFY THE OCCUPANCY GROUP OF
 THE BUILDING AND CLASSIFY THE OCCUPANCY OF ALL THE
 PROPOSED SPACES AS REQUIRED BY SEC. 302.1 FBC-BUILDING.
 SPECIFY THE USE, NUMBER AND AGES OF CHILDREN IN THE
 TODDLER AREA AND CHECK IN AREA. WHO USES THE CHECK IN
 KIOSKS.
  
 3- ARCHITECT TO PROVIDE ALL THE MINIMUM PLAN REVIEW
 CRITERIA AS REQUIRED BY SEC. 107.3.5 CITY AMENDMENTS.
 SPECIFY TYPE OF CONSTRUCTION, RISK CATEGORY,
 SPRINKLERED OR NON-SPRINKLERED BUILDING, OCCUPANCY
 GROUP,
  
 4- THERE ARE SEVERAL BUILDINGS ON THIS PROPERTY.
 PROVIDE SITE PLAN/PLOT PLAN SHOWING THE BUILDING AND
 AREA OF WORK. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- PROVIDE LIFE-SAFETY PLANS SHOWING OCCUPANT LOAD
 (SEC. 1004.1.1 FBC-BUILDING), ALL EXIT SIGNS SEC.
 1013.1 FBC-BUILDING.
  
 6- EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS. SEC. 1016.2
 FBC-BUILDING. SEE NEW DOOR #100. REVISE OR SHOW HOW IT
 WILL BE ALLOWED TO PASS THRU THE DAY CARE AREA.
 NOTE: COORDINATE WITH TOTAL OCCUPANT LOAD REQUESTED ON
 ITEM #5 ABOVE IF DETERMINED THAT PASSING THRU THE NEW
 DAY CARE AREA FOR TODDLERS MAY BE ALLOWED.
  
 7- PLANS SHOW A 2 HOUR FIRE RATED CEILING SEPARATION
 ASSEMBLY UL DES U438 FOR NEW STORAGE ROOM. THIS NEW
 STORAGE ROOM IS LOCATED IN THE EXISTING SHAFT. THE
 SPECIFIED CEILING ASSEMBLY IS A WALL ASSEMBLY NOT A
 CEILING ASSEMBLY. NEED TO SPECIFY AN APPROVED
 HORIZONTAL ASSEMBLY ASSEMBLY COMPLYING WITH SEC.
 711.2.2 FBC AS REQUIRED BY SEC. 713.5 FBC.
  
 8- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR NEW
 STORAGE FLOOR FRAMING. SPECIFY ALL STRUCTURAL
 FASTENERS. SEC. 1604.1 FBC.
  
 9- PROVIDE DETAILS AND SPECIFICATIONS FOR ALL BUILT
 IN-ELEMENTS SHOWING COMPLIANCE WITH SEC. 904 FBC
 ACCESSIBILITY AS REQUIRED BY SEC. 227
 FBC-ACCESSIBILITY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,