| 2019-07-24 14:06:45 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- FLAT ROOF NOA 17-0824.11 SUBMITTED: SELECTED |
| | ASSEMBLY ON PAGE 27 OF 32 DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED |
| | RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER |
| | AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7 |
| | ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE |
| | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |