1 |
|
| Notes |
| Date |
Text |
| 2019-08-04 08:21:24 | 8/4/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH | | | COMMENTS NOTE - A COMPREHENSIVE REVIEW COULD NOT BE | | | DONE AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS | | | MAY BE GENERATED UPON THE RE-REVIEW OF SUBMITTED | | | CORRECTIONS. | | | | | | | | | | | | A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE | | | PROPOSED BACKFLOW PREVENTION DEVICE, THIS CAN BE DONE | | | BY GOING TO THE PROPERTY APPRAISER WEBSITE AND PRINT | | | OUT A STRUCTURAL LAYOUT OF THE BUILDING AND HAND DRAW | | | THE METER LOCATION WITH THE BACKFLOW | | | | | | THIS BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS | | | REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY | | | DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION | | | MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/ | | | PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN | | | ECTION-CONTROL-MANUAL FOR MORE INFORMATION. THE 975XL | | | WATKINS MODEL IS NOT LEAD-FREE AS THE 975XL2 IS SO | | | PLEASE RESUBMIT SPECS FOR IT. | | | | | | SUBMIT A SEPERATE PERMIT FOR THE BACKFLOW | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLANS EXAMINER | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | | | | | | | |
|