Plan Review Notes
Plan Review Notes For Permit 19071132
Permit Number 19071132
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-24 16:53:11RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- THIS ROOFING WORK IS FOR ST. MARY'S HOSPITAL.
 HOSPITALS ARE ESSENTIAL FACILITIES. ENGINEER DOING THE
 RAS 117 CALCULATIONS NEED TO REVISE THE DESIGN CRITERIA
 ACCORDINGLY. ENGINEER TO SEE SEC. 1603.1.4, SEC. 1604.5
 AND SEC. 1609.3 FBC-BUILDING AND REVISE DESIGN CRITERIA
 AND RAS 117 CALCULATIONS AS REQUIRED.
  
 2- IT LOOKS LIKE THERE ARE SEVERAL BUILDINGS WHERE WORK
 IS GOING TO BE PERFORMED. THIS IS A VERY LARGE COMPLEX.
 IT IS NOT CLEAR WHICH BUILDINGS ARE INVOLVED. PROVIDE A
 PLOT PLAN SHOWING EACH BUILDING. AND PROVIDE A PERMIT
 APPLICATION FOR EACH BUILDING TO FACILITATE INSPECTIONS
 AND RECORD KEEPING. SEC. 105.1.1 CITY AMENDMENTS, SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- STEEL DECK NOA 15-0709.15 SUBMITTED: PROVIDE THE THE
 FIELD RESISTANCE TEST (TAS 105) AS REQUIRED BY THE
 STEEL DECK LIMITATIONS ON LAST PAGE OF THE NOA
 SUBMITTED.
  
 4- WATERPROOFING NOA 18-0717.02: SELECTED ASSEMBLY ON
 PAGE 15 OF 25 IS LIMITED BY GENERAL LIMITATION #9. THE
 DESIGN PRESSURES FOR THIS SYSTEM ARE TOO LOW. THIS
 SYSTEM CAN NOT BE USED BECAUSE GENERAL LIMITATION #9
 DOESN'T ALLOW ANY ENHANCEMENT. SEE GENERAL LIMITATION
 #9. REVISE AS REQUIRED.
 SEC. 1609.3 FBC-BUILDING
  
 5- ALL THE NOA'S SUBMITTED ARE MISSING THE LAST PAGE.
 THIS PAGE CONTAINS ALL THE SYSTEMS LIMITATIONS AND
 GENERAL LIMITATIONS. PROVIDE COPIES OF THE LAST PAGE.
 FAC61G20-3.001
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved