| 2019-08-14 12:00:58 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE KITCHEN SINK IS NOT SHOWN ON THE SANITARY |
| | ISOMETRIC ALL FIXTURES SHALL BE SHOWN TO MATCH FLOOR |
| | PLAN. PER WPB AMEND TO FBC 107.3.5.3(12) |
| | |
| | 2. THE SANITARY ISOMETRIC SHOWS A WASHING MACHINE |
| | PLEASE SHOW LOCATION OF WASHING MACHINE ON FLOOR PLAN. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. IF AN AIR ADMITTANCE VALVE IS BEING USED FOR THE |
| | WASHING MACHINE THE HORIZONTAL DRAIN SHALL BE MIN OF |
| | 3IN PER MANUFACTURE INSTALLATION GUIDE. |
| | |
| | 4. THE FLOOR PLAN SHOWS A SHOWER AND THE ISOMETRIC |
| | DRAWING IS SHOWING A TUB PLEASE CLARIFY. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 5. PLEASE SHOW LOCATION, SIZE AND TYPE OF WATER HEATER. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |