| 2019-08-07 15:20:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 |
| | 2. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9 |
| | 3. RISER DIAGRAM SHOWS THE INTERSYSTEM BONDING |
| | TERMINATION POINT MOUNTED TO 2 INCH PVC. THIS SHOULD BE |
| | INSTALLED ON THE GROUNDING ELECTRODE CONDUCTOR. PROVIDE |
| | CORRECITON. NEC 250.94 |
| | 4. THE 2 INCH PVC RISER WILL BE SUBJECT TO PHYSICAL |
| | DAMAGE AND SHOULD BE SCHEDULE 80 PVC. PROVIDE |
| | CORRECTION. NEC 352.12 |
| | 5. FOR UNIT A, A GFCI PROTECTED RECEPTACLE OUTLET ON A |
| | 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| | THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR |
| | PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN |
| | COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON |
| | THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3), 210.52(D) |
| | 6. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |