| Plan Review Notes For Permit 19071050 |
| Permit Number |
19071050 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-30 06:42:15 | 1) SHT. 1 OF 1 - THE SHEET CONTAINING THE TOTAL DYNAMIC | | | HEAD CALCULATION IS PRACTICABLY ILLEGIBLE DUE TO THE | | | SMALL PRINTING. THIS PAGE IS CONSTANTLY BEING SUBMITTED | | | AND REJECTED FOR THE SAME REASONS. IT IS DIFFICULT TO | | | READ. PLEASE PLACE THIS INFORMATION ON A SEPARATE SHEET | | | AND EXPAND IT SO ALL INFORMATION IS LEGIBLE AND CLEAR | | | IN DETAIL. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHT. 2 OF 4 - THE INFORMATION IN THE BOX FOR THE | | | "SPA ONLY" NOTES THE MAXIMUM FLOW SYSTEM RATE IS FROM | | | THE PUMP CURVE. THE MAXIMUM FLOW OF THE PUMP FROM ITS | | | PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD | | | CALCULATION IS NO LONGER ALLOWED TO BE USED IN | | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | | 7 - 2013 SECS. 4.4.9, 4.4.9.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|