Plan Review Notes
Plan Review Notes For Permit 19071050
Permit Number 19071050
Review Stop P
Sequence Number 2
Notes
Date Text
2019-08-30 06:42:151) SHT. 1 OF 1 - THE SHEET CONTAINING THE TOTAL DYNAMIC
 HEAD CALCULATION IS PRACTICABLY ILLEGIBLE DUE TO THE
 SMALL PRINTING. THIS PAGE IS CONSTANTLY BEING SUBMITTED
 AND REJECTED FOR THE SAME REASONS. IT IS DIFFICULT TO
 READ. PLEASE PLACE THIS INFORMATION ON A SEPARATE SHEET
 AND EXPAND IT SO ALL INFORMATION IS LEGIBLE AND CLEAR
 IN DETAIL. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. 2 OF 4 - THE INFORMATION IN THE BOX FOR THE
 "SPA ONLY" NOTES THE MAXIMUM FLOW SYSTEM RATE IS FROM
 THE PUMP CURVE. THE MAXIMUM FLOW OF THE PUMP FROM ITS
 PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD
 CALCULATION IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  