| 2019-09-16 10:30:24 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | |
| | ARCHITECTS-ENGINEERS |
| | FLORIDA STATUTE 553.80(2)(B): |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- STRUCTURAL PLANS SUBMITTED ARE FOR THE INSTALLATION |
| | OF SOLAR PV SYSTEMS ON ROOFS WITH ROOF TILES. THIS IS A |
| | HOUSE WITH ROOF SHINGLES. THE PROPOSED INSTALLATION |
| | DOESN'T MATCH ACTUAL CONDITIONS. REVISE AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | PLANS SUBMITTED ARE THE SAME. NO CHANGES WERE DONE. |
| | PLANS DON'T APPLY TO THE PROPOSED SITE SPECIFIC |
| | INSTALLATION. PROVIDE COMPLETE DRAWINGS FOR SITE |
| | SPECIFIC INSTALLATION. |
| | NOTE: CONTRACTOR STATED ON THE RE-SUBMITTAL FORM THAT |
| | SOLAR PANELS ARE GOING TO BE INSTALLED ON THE FLAT ROOF |
| | OF THE HOUSE. PLANS AND DESIGN CRITERIA NEED TO MATCH |
| | THIS PROPOSED INSTALLATION. REVISE PLANS AS REQUIRED TO |
| | MATCH PROPOSED INSTALLATION. |
| | SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 2- STRUCTURAL ATTACHMENT TO THE ROOF OF THE HOUSE IS |
| | NOT CLEAR. FLORIDA PRODUCT APPROVAL FL21074.R4 |
| | REFERENCED ON DRAWING S-03 IS ONLY FOR THE "ROOF SOLAR |
| | PEDESTAL". THIS PRODUCT APPROVAL ONLY EVALUATES THE |
| | SOLAR PEDESTAL ADHERED TO TOP OF FOAM ADHESIVE. ALSO, |
| | THE DESIGN OF THE ROOF ADHESIVE TO THE BUILDING |
| | STRUCTURE IS OUTSIDE THE SCOPE OF THIS PRODUCT |
| | APPROVAL. SEE ITEMS # 12.1 AND 12.2 OF THE LIMITATIONS |
| | AND CONDITIONS OF USE ON PAGE 3 OF 7 OF THIS PRODUCT |
| | APPROVAL. ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE |
| | DESIGN ANALYSIS AND DETAILS/SPECIFICATIONS SHOWING THE |
| | DESIGN ATTACHMENT OF THE FOAM ADHESIVE TO THE BUILDING |
| | STRUCTURE. NEED TO SHOW HOW THE SURFACE RECEIVING THE |
| | FOAM ADHESIVE WILL TRANSFER THE LOADS. SEC. 107.2.1.2 |
| | CITY AMENDMENTS AND SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: KEEP IN CONSIDERATION THAT THIS HOUSE HAS ROOF |
| | SHINGLES. ALSO, NEED PRODUCT APPROVAL FOR FOAM ADHESIVE |
| | LISTING THE SURFACE WHERE THE FOAM IS GOING TO BE |
| | ADHERED TO. |
| | |
| | RESPONSE: |
| | ENGINEER DIDN'T PROVIDE A COMPLETE SITE SPECIFIC DESIGN |
| | ANALYSIS AND DETAILS/SPECIFICATIONS SHOWING THE LOAD |
| | PATH FROM THE ADHESIVE TO THE EXISTING ROOF STRUCTURE. |
| | ENGINEER TO COORDINATE COMPLETE ANALYSIS AND |
| | DETAILS/SPECIFICATIONS WITH THE PROPOSED INSTALLATION |
| | ON THE EXISTING FLAT ROOF AS SPECIFIED BY THE |
| | CONTRACTOR SUBMITTING THE PERMIT APPLICATION. |
| | NOTE: EXISTING ROOF WAS REPLACED IN 2003. UPLIFT TEST |
| | MAY BE REQUIRED TO DEMONSTRATE THAT EXISTING ROOF |
| | MEMBRANE WILL RESISTS THE ADDITIONAL WIND LOADS. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 3- ENGINEER OF RECORD NEEDS TO PROVIDE ALL HIS |
| | INFORMATION ON THE TITLE BLOCK OF ALL DRAWINGS AS |
| | REQUIRED BY SEC. 61G15-23.001(4) F.A.C. |
| | |
| | RESPONSE: |
| | ENGINEER'S INFORMATION IS NOT PROVIDED ON THE TILE |
| | BLOCK OF DRAWINGS SUBMITTED. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | SEC. 61G20-3.001 F.A.C. FOR: |
| | A) ROOF SOLAR PEDESTAL SPECIFIED ON PLANS. |
| | |
| | RESPONSE: |
| | ONE ONE COPY SUBMITTED. NEED TWO COPIES. |
| | |
| | ORIGINAL COMMENT: |
| | B) FOAM ADHESIVE SPECIFIED ON PLANS. NEED PRODUCT |
| | APPROVAL FOR FOAM ADHESIVE LISTING THE SURFACE WHERE |
| | THE FOAM IS GOING TO BE ADHERED TO. |
| | |
| | RESPONSE: |
| | NEED PRODUCT APPROVAL LISTING THE SURFACE WHERE THE |
| | FOAM IS GOING TO BE ADHERED TO. PRODUCT APPROVAL |
| | SUBMITTED IS FOR INSTALLATION ON ROOF TILE UNDERLAYMENT |
| | ONLY. |
| | |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |