| Plan Review Notes For Permit 19071032 |
| Permit Number |
19071032 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-20 13:03:28 | PLAN DENIED | | | 1) REFER TO SECTION 601.6 BALANCED RETURN AIR | | | 2017 FBC (M) | | | 2) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S | | | 2017 FBC (M) NO COMBUSTIBLES IN RETURN AIR PLENUM | | | INCLUDING DOOR. | | | 3) PROVIDE MINIMUM VENTILATION RATES PER TABLE | | | 403.3.1.1 | | | 2017 FBC (M) ON PLANS. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|