Plan Review Notes
Plan Review Notes For Permit 19071032
Permit Number 19071032
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-07-23 14:51:54 
  
  
  
 1) SHEET TS - THERE ARE INCORRECT REFERNCES TO CURRENT
 FIRE CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, NATIONAL
 ELECTRICAL CODE? 2014 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND CORRECT.
  
  
  
  
  
 2) SHEET A 4 - THERE ARE INDICATIONS OF AN EXISITNG
 RAMP.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS.
  
 TABLE 7.2.5.3(B) EXISTING RAMPS DIMENSIONAL CRITERIA -
 FEATURE FT/IN. MM MINIMUM WIDTH MAXIMUM SLOPE MAXIMUM
 HEIGHT BETWEEN LANDINGS
 30 INC. (760) 1 IN 8 (3660) 12 FT
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE.
  
  
  
  
 3) SHEET A 4 - THE ARE INDICATIONS OF NEW AND EXISTING
 HANDRAILS AND GUARDS WITH LIMITED DETAILS
  
 PER NFPA 101, CH 7, MEANS OF EGRESS.
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT
 THE SIDES OF
 STAIRS BY 7.2.2.4.1.1, BOTH OF THE FOLLOWING PROVISIONS
 SHALL APPLY:
 (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN
 30 IN. (760
 MM) OF ALL PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (2) FOR EXISTING STAIRS, HANDRAILS SHALL MEET THE
 FOLLOWING CRITERIA:
 (A) THEY SHALL BE PROVIDED WITHIN 44 IN. (1120 MM) OF
 ALL
 PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (B) SUCH STAIRS SHALL NOT HAVE THEIR EGRESS CAPACITY
 ADJUSTED
 TO A HIGHER OCCUPANT LOAD THAN PERMITTED BY THE
 CAPACITY
 FACTOR IN TABLE 7.3.3.1 IF THE STAIR?S CLEAR WIDTH
 BETWEEN
 HANDRAILS EXCEEDS 60 IN. (1525 MM).
  
 7.2.2.4.5.1 NEW HANDRAILS ON STAIRS SHALL BE NOT LESS
 THAN 34 IN.
 (865 MM), AND NOT MORE THAN 38 IN. (965 MM), ABOVE THE
 SURFACE
 OF THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE
 RAIL FROM THE
 LEADING EDGE OF THE TREAD.
 7.2.2.4.5.2 EXISTING REQUIRED HANDRAILS SHALL BE NOT
 LESS THAN 30 IN.
 (760 MM), AND NOT MORE THAN 38 IN. (965 MM), ABOVE THE
 SURFACE
 OF THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE
 RAIL FROM THE
 LEADING EDGE OF THE TREAD.
 7.2.2.4.5.3 THE HEIGHT OF REQUIRED HANDRAILS THAT FORM
 PART OF A
 GUARD SHALL BE PERMITTED TO EXCEED 38 IN. (965 MM), BUT
 SHALL NOT
 EXCEED 42 IN. (1065 MM), MEASURED VERTICALLY TO THE TOP
 OF THE RAIL
 FROM THE LEADING EDGE OF THE TREAD.
  
 7.2.2.4.6.1 THE HEIGHT OF GUARDS REQUIRED IN 7.1.8
 SHALL BE
 MEASURED VERTICALLY TO THE TOP OF THE GUARD FROM THE
 SURFACE
 ADJACENT THERETO.
 7.2.2.4.6.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065
 MM) HIGH,
 EXCEPT AS PERMITTED BY ONE OF THE FOLLOWING:
 (1) EXISTING GUARDS WITHIN DWELLING UNITS SHALL BE
 PERMITTED TO
 BE NOT LESS THAN 36 IN. (915 MM) HIGH.
 (2) THE REQUIREMENT OF 7.2.2.4.6.2 SHALL NOT APPLY IN
 ASSEMBLY
 OCCUPANCIES WHERE OTHERWISE PROVIDED IN CHAPTERS 12 AND
 13.
 (3) *EXISTING GUARDS ON EXISTING STAIRS SHALL BE
 PERMITTED TO BE
 NOT LESS THAN 30 IN. (760 MM) HIGH.
 7.2.2.4.6.3* OPEN GUARDS, OTHER THAN APPROVED EXISTING
 OPEN
 GUARDS, SHALL HAVE INTERMEDIATE RAILS OR AN ORNAMENTAL
 PATTERN SUCH
 THAT A SPHERE 4 IN. (100 MM) IN DIAMETER IS NOT ABLE TO
 PASS
 THROUGH ANY OPENING UP TO A HEIGHT OF 34 IN. (865 MM),
 AND THE
 FOLLOWING ALSO SHALL APPLY:
 (1) THE TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD,
 AND
 BOTTOM ELEMENT OF A GUARDRAIL AT THE OPEN SIDE OF A
 STAIR SHALL
 BE OF SUCH SIZE THAT A SPHERE 6 IN. (150 MM) IN
 DIAMETER IS
 NOT ABLE TO PASS THROUGH THE TRIANGULAR OPENING.
 (2) IN DETENTION AND CORRECTIONAL OCCUPANCIES, IN
 INDUSTRIAL
 OCCUPANCIES, AND IN STORAGE OCCUPANCIES, THE CLEAR
 DISTANCE
 BETWEEN INTERMEDIATE RAILS, MEASURED AT RIGHT ANGLES TO
 THE
 RAILS, SHALL NOT EXCEED 21 IN. (535 MM).
  
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 4) THERE IS NO INDICATIONS OF A DOOR SCHEDULE AND/OR
 EXIT DOOR HARDWARE/LOCKS.
  
 PER NFPA 101, CH 38 NEW BUSINESS OCCUPANCIES AND CH 7
 MEANS OF EGRESS
  
 38.2.2 MEANS OF EGRESS COMPONENTS.
 38.2.2.1 GENERAL. MEANS OF EGRESS COMPONENTS SHALL BE
 LIMITED
 TO THE TYPES DESCRIBED IN 38.2.2.2 THROUGH 38.2.2.12.
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL
 ENTRANCE THAT IS
 REQUIRED TO SERVE AS AN EXIT SHALL BE DESIGNED AND
 CONSTRUCTED SO
 THAT THE PATH OF EGRESS TRAVEL IS OBVIOUS AND DIRECT.
 WINDOWS THAT,
 BECAUSE OF THEIR PHYSICAL CONFIGURATION OR DESIGN AND
 THE MATERIALS
 USED IN THEIR CONSTRUCTION, HAVE THE POTENTIAL TO BE
 MISTAKEN FOR
 DOOR OPENINGS SHALL BE MADE INACCESSIBLE TO THE
 OCCUPANTS BY
 BARRIERS OR RAILINGS.
 7.2.1.1.3 OCCUPIED BUILDING.
 7.2.1.1.3.1 FOR THE PURPOSES OF SECTION 7.2, A BUILDING
 SHALL BE
 CONSIDERED TO BE OCCUPIED AT ANY TIME IT MEETS ANY OF
 THE
 FOLLOWING CRITERIA:
 (1) IT IS OPEN FOR GENERAL OCCUPANCY.
 (2) IT IS OPEN TO THE PUBLIC.
 (3) IT IS OCCUPIED BY MORE THAN 10 PERSONS.
 7.2.1.1.3.2 WHERE MEANS OF EGRESS DOORS ARE LOCKED IN A
 BUILDING
 THAT IS NOT CONSIDERED OCCUPIED, OCCUPANTS SHALL NOT BE
 LOCKED
 BEYOND THEIR CONTROL IN BUILDINGS OR BUILDING SPACES,
 EXCEPT FOR
 LOCKUPS IN ACCORDANCE WITH 22.4.5 AND 23.4.5, DETENTION
 AND
 CORRECTIONAL OCCUPANCIES, AND HEALTH CARE OCCUPANCIES.
  
 7.2.1.2.3 MINIMUM DOOR LEAF WIDTH.
 7.2.1.2.3.1 FOR PURPOSES OF DETERMINING MINIMUM DOOR
 OPENING
 WIDTH, THE CLEAR WIDTH IN ACCORDANCE WITH 7.2.1.2.1
 SHALL BE USED,
 UNLESS DOOR LEAF WIDTH IS SPECIFIED.
 7.2.1.2.3.2 DOOR OPENINGS IN MEANS OF EGRESS SHALL BE
 NOT LESS
 THAN 32 IN. (810 MM) IN CLEAR WIDTH, EXCEPT UNDER ANY
 OF THE
 FOLLOWING CONDITIONS:
 (1) WHERE A PAIR OF DOOR LEAVES IS PROVIDED, ONE DOOR
 LEAF SHALL
 PROVIDE NOT LESS THAN A 32 IN. (810 MM) CLEAR WIDTH
 OPENING.
 (2)* EXIT ACCESS DOOR ASSEMBLIES SERVING A ROOM NOT
 EXCEEDING 70
 FT2 (6.5 M2) AND NOT REQUIRED TO BE ACCESSIBLE TO
 PERSONS WITH
 SEVERE MOBILITY IMPAIRMENTS SHALL BE NOT LESS THAN 24
 IN.
 (610 MM) IN DOOR LEAF WIDTH.
 (3)* DOOR OPENINGS SERVING A BUILDING OR PORTION
 THEREOF NOT
 REQUIRED TO BE ACCESSIBLE TO PERSONS WITH SEVERE
 MOBILITY
 IMPAIRMENTS SHALL BE PERMITTED TO BE 28 IN. (710 MM) IN
 DOOR
 LEAF WIDTH.
 (4) IN EXISTING BUILDINGS, THE EXISTING DOOR LEAF WIDTH
 SHALL BE NOT
 LESS THAN 28 IN. (710 MM).
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND PROVIDE DETAILS WITHIN A DOOR
 SCHEDULE IN COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  