Plan Review Notes
Plan Review Notes For Permit 19071032
Permit Number 19071032
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-07 09:41:432017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19071032
 ADD: 1014 N. OLIVE AVE.
 CONT: OCEAN ONE MARINE
 TEL: 561-315-4916
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 07/2019
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE PAPER AND HAVE AN ELECTRONIC
 SIGNATURE AND SEAL BY ALLEN WIEDER P. E.
 61G15-23.003 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 2) THE COVERSHEET HAS A SITE PLAN THAT IS IN 1 INCH =
 20 FEET. THIS IS A SMALLER SCALE THAN ALLOWED BY THE
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.3
 QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE. PLEASE CORRECT.
 3) WITHIN THIS PLAN THERE IS NO CODE ANALYSIS & MINIMUM
 BUILDING TYPE:
 3A) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP
  
 3B) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE SECTION 504.3, TABLE 504.4 & TABLE 506.2).
  
 3C) WITH THE CLOSENESS OF THE 2 BUILDINGS IS THERE AN
 ASSUMED PROPERTY LINE BETWEEN THE 2 BUILDINGS OR ARE
 YOU CONSIDERING THIS AS ONE BUILDING ON THE SAME LOT IN
 ACCORDANCE WITH 2017 FBC-B 503.1.2. PLEASE ALSO PROVIDE
 THE TOTAL SQ. FT. OF AREA FOR EACH BUILDING.
 ASSUMED PROPERTY LINE FBC-B 503.1.2.
 RATED EXTERIOR WALLS FBC-B TABLE 602
 ALLOWABLE AREA OPENINGS IN FIRE RATED EXTERIOR WALLS
 TABLE 705.8.
  
 3D) IS THERE A CHANGE OF OCCUPANCY FOR BOTH AND OR
 EITHER BUILDING? 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED. CHAPTER 10 OF THE 2017 EXISTING BUILDING
 CODE.
  
 3D) TO WHICH DESIGN CRITERIA WERE THE PLANS DEVELOPED
 UNDER THE 2017 FLORIDA BUILDING CODE EXISTING BUILDING
 CODE THE PLANS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE DESIGN PROFESSIONAL.
  
 4) WITHIN THIS PLAN SET THERE IS NO REFERENCE TO A LIFE
 SAFETY PLAN SHOWING COMPLIANCE WITH:
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 LIFE SAFETY PLAN:
 OCCUPANCY TYPE
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 5) THE SITE PLAN DOES NOT SHOW:
 5A) ACCESSIBLE PARKING SPACE. 2017 FBC-ACCESSIBILITY
 CODE TABLE 208.2.
  
 5B) THE PLANS DO NOT STATE THE USAGE FOR THIS PROJECT,
 IF THE USAGE IS GOING TO BE ASSOCIATED WITH
 REHABILITATION AND OR OUTPATIENT THERAPY THEN SHOW
 COMPLIANCE WITH:
 2017 ACCESS. CODE SECTION 208.2.2 REHABILITATION
 FACILITIES AND OUTPATIENT PHYSICAL THERAPY FACILITIES.
 TWENTY PERCENT OF PATIENT AND VISITOR PARKING SPACES
 PROVIDED TO SERVE REHABILITATION FACILITIES
 SPECIALIZING IN TREATING CONDITIONS THAT AFFECT
 MOBILITY AND OUTPATIENT PHYSICAL THERAPY FACILITIES
 SHALL COMPLY WITH 502.
  
 5C) PLEASE SHOW COMPLIANCE WITH ACCESSIBLE PARKING
 SPACE & ACCESS AISLE SIZE IN ACCORDANCE WITH ACCESS.
 CODE 502.2. & 502.3.
  
 5D) CITY ACCESSIBLE PARKING STANDARD. AN ACCESSIBLE
 PARKING SPACE AND ACCESS AISLE, PLEASE SEE THE 2017
 FBC-ACCESSIBILITY CODE 502.3.3 MARKING. ACCESS AISLES
 SHALL BE MARKED SO AS TO DISCOURAGE PARKING IN THEM.
 THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
  
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED. FLORIDA
 LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL STRIPING OF
 ACCESS AISLES.
 THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDES A DOUBLE LINED DIMENSIONED PARKING
 STALL DETAIL.
  
 5E) PLEASE PROVIDE COMPLIANCE WITH THE 2017 FBC-ACCESS.
 CODE SECTION:
 206.2.2 WITHIN A SITE. AT LEAST ONE ACCESSIBLE ROUTE
 SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE
 FACILITIES, ACCESSIBLE ELEMENTS, AND ACCESSIBLE SPACES
 THAT ARE ON THE SAME SITE.
  
 6) FLOOR PLAN SHEET A-2:
 6A) THE FLOOR PLAN BLDG. # 1 THE WEST BUILDING SHOWS 3
 SETS OF STAIRS TO GAIN ENTRY INTO THIS BUILDING, THIS
 BUILDING HAS NO ACCESSIBLE EGRESS. SHOW HOW AN
 ACCESSIBLE EGRESS WILL BE COMPLIED WITH FOR THIS
 BUILDING.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 6B) THERE ARE 2 EXISTING RESTROOMS IN BLDG. # 1 (WEST
 BLDG.) NEITHER IS DESIGNATED AS AN ACCESSIBLE RESTROOM.
 RESTROOM # 2 DOES SHOW GRAB BARS AT THE WATER CLOSET
 (ASSUMED TO BE THE ACCESSIBLE RESTROOM). PLEASE
 ACKNOWLEDGE. RESTROOM IS NOT DIMENSIONED ON SHEET A2 OR
 RESTROOM ELEVATIONS A6, CANNOT DETERMINE THE EXACT SIZE
 AND ACCESSIBILITY REQUIREMENTS.
  
 6C) EXISTING RESTROOM # 2 IN THE WEST BUILDING THE LAV
 IS IN THE CLEAR FLOOR SPACE REQUIRED FOR THE
 WATERCLOSET.
 2017 ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 2017 ACCESS. CODE 604.3.2 OVERLAP. THE REQUIRED
 CLEARANCE AROUND THE WATER CLOSET SHALL BE PERMITTED TO
 OVERLAP THE WATER CLOSET, ASSOCIATED GRAB BARS,
 DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT HOOKS,
 SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE AND
 CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE TURNING
 SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
 LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 6D) SHEET A6 RESTROOM 2 ELEVATION 12 DEPICTS THE LAV
 AND MIRROR ABOVE. THERE IS NO DIMENSION TO THE BOTTOM
 REFLECTIVE SURFACE OF THE MIRROR SHOWING COMPLIANCE
 WITH:
 2017 ACCESS. CODE SECTION CODE 603.3 MIRRORS. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 6E) THERE IS NO ROOM IDENTIFICATION TAGS GIVEN TO THE
 ROOMS TO IDENTIFY PROBLEM AREAS WITH THE ROOMS (3
 OFFICES). 107.2.1.2. THERE IS NO FURNITURE PLAN
 PROVIDED AS WELL.
  
 6F) SHEET A2 THERE ARE NO DOOR IDENTIFICATION TAGS
 IDENTIFYING NEW / OLD DOORS, SIZE OF DOORS NOR DOOR
 SCHEDULE FOUND. 2017 FBC-B 1010.1.1 DOOR SIZE.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 6G) THE FLOOR PLAN SHEET A2 INDICATES ELEVATIONS FOR
 KITCHEN ON SHEET A-6 DETAILS 1-4. DETAIL # 1 INDICATES
 THE COUNTER TOP/ SINK HEIGHT FROM FINISH FLOOR IS 36
 INCHES TALL. PLEASE PROVIDE COMPLIANCE WITH:
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6H) THE FLOOR PLAN DOES NOT SHOW IF THE KITCHEN SINK IS
 TO BE A FORWARD APPROACH OR SIDE APPROACH SEE:
 ACCESS. CODE SECTION 606.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED. IF A FORWARD APPROACH IS TO
 BE USED THE N SHOW THE REMOVAL OF THE CLEAR FLOOR
 SPACE, TOE KICK AND DOORS.
 EXCEPTION:
 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE
 PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK
 TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET
 BARS.
  
 6I) NOT USED.
  
 7) SHEET A2 BUILDING # 2 THE EAST BUILDING:
 7A) PLEASE SHOW WHICH DOORWAY IS THE MAIN ENTRY AND AN
 ACCESSIBLE EGRESS INTO THIS BUILDING? SHOW HOW AN
 ACCESSIBLE EGRESS WILL BE COMPLIED WITH FOR THIS
 BUILDING.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 7B) SHEET A2 BUILDING # 2 SHOWS AN ACCESSIBLE BATHROOM
 AND PROPOSED SHOWER STALL. THE SIZE OF THE PROPOSED
 SHOWER STALL IS 3 FEET X 4 FEET IN LENGTH. PLEASE SEE
 THE 2017 ACCESS. CODE FOR THE MINIMUM SIZE OF SHOWER
 STALLS. ACCESS. CODE 608.2.
 608.2.1 TRANSFER STALLS ? MINIMUM STALL SIZE OF 36
 INCHES X 36 INCHES.
 608.2.2. STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS 36
 INCHES X 60 INCHES AND SHALL HAVE A 60 INCHES WIDE
 MINIMUM ENTRY ON THE FACE OF THE SHOWER COMPARTMENT.
 NOT THE END OF A SHOWER STALL, THIS IS AN ACCESSIBLE
 SHOWER STALL.
  
 7C) SHEET A6 DETAIL 13 THE ACCESSIBLE ROLL-IN SHOWER
 SHOWS A CURB AT THE ENTRY. ROLL-IN SHOWERS HAVE NO
 CURBS, THEY ARE ROLL-IN TYPE SHOWERS. PLEASE REDESIGN
 THE SHOWER TO COMPLY WITH ALL OF THE REQUIREMENTS FOUND
 FOR ACCESSIBLE ROLL-IN SHOWERS ACCESS. CODE 608.2.2 OR
 608.2.3.
  
 7D) THERE IS NO ROOM IDENTIFICATION TAGS GIVEN TO THE
 ROOMS TO IDENTIFY PROBLEM AREAS WITH THE ROOMS (3
 OFFICES). 107.2.1.2. THERE IS NO FURNITURE PLAN
 PROVIDED AS WELL.
  
 7E) SHEET A2 THERE ARE NO DOOR IDENTIFICATION TAGS
 IDENTIFYING NEW / OLD DOORS, SIZE OF DOORS NOR DOOR
 SCHEDULE FOUND. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED. 2017 FBC-B 1010.1.1 DOOR SIZE.
  
 7F) THE FLOOR PLAN SHOWS THE ACCESSIBLE BATHROOM, SHEET
 A6 DETAIL 14 SHOWS THE LAV AND MIRROR.
 THERE IS NO DIMENSION TO THE BOTTOM REFLECTIVE SURFACE
 OF THE MIRROR SHOWING COMPLIANCE WITH:
 2017 ACCESS. CODE SECTION CODE 603.3 MIRRORS. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 8) THERE IS NO REFLECTIVE CEILING PLAN WITH THE
 EXCEPTION OF SHEET A-5 AN ELECTRICAL OUTLET AND CEILING
 FIXTURE PLAN. PLEASE PROVIDE COMPLIANCE WITH: 2017
 FBC-B:
  
 8A) 1209.2 ATTIC SPACES. AN OPENING NOT LESS THAN 20
 INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE
 PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF
 OVER 30 INCHES (762 MM). CLEAR HEADROOM OF NOT LESS
 THAN 30 INCHES (762 MM) SHALL BE PROVIDED IN THE ATTIC
 SPACE AT OR ABOVE THE ACCESS OPENING.
  
  
 8B) 1209.3 MECHANICAL APPLIANCES. ACCESS TO MECHANICAL
 APPLIANCES INSTALLED IN UNDER-FLOOR AREAS, IN ATTIC
 SPACES AND ON ROOFS OR ELEVATED STRUCTURES SHALL BE IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL.
  
 9) PLEASE CORRECT THE PAGE NUMBERING, THERE ARE 2
 SHEETS IDENTIFIED AS S-3 AND NO SHEET S-4. TYPO.
  
 10) INFORMATIONAL: THE PRESSURES (IN VASD) FOUND ON
 SHEET S-3 FOR COMPONENTS AND CLADDING ARE GOOD FOR ALL
 PRESSURE ZONES 1-5. THE PRODUCT APPROVALS FOR
 COMPONENTS AND CLADDING CAN BE DEFERRED BY EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 11A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS.
 (B) WINDOWS & MULLIONS.
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS.
  
 11B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 12) PLEASE NOTE THERE ARE WELDED AND BOLTED CONNECTIONS
 WITH-IN THE PROJECT. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION. IN
 ACCORDANCE WITH THE AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING / 2017 FBC-B 2204.2 BOLTING.
 FOR FURTHER QUESTIONS ABOUT THIS COMMENT, PLEASE
 CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD AT
 561-805-6666.
  
 13) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy