Notes
Date Text
2020-03-14 10:31:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1) 107.5.3 FBC[AMENDED]PLEASE REMOVE PLAN SHEETS A-1.0
 TO A-4.1 FROM BOTH SETS AS THESE ARE FOR WORK THAT IS
 ISSUED UNDER SEPARATE PERMIT.
  
 2ND REVIEW, PAGES NOT REMOVED.
  
 2) 503.3 FBC[CE] BUILDING ENVELOPE. NEW BUILDING
 ENVELOPE ASSEMBLIES THAT ARE PART OF THE ALTERATION
 SHALL COMPLY WITH SECTIONS C402.1 THROUGH C402.5.
 -PROVIDE INSULATION TYPE AND LOCATION FOR THE NEWLY
 CREATED ROOF AREA.
  
 2ND REVIEW, RESPONSE LETTER DOES NOT STATE WHERE THIS
 WAS REVISED ON THE PLAN AND I WAS UNABLE TO LOCATE IT;
 EITHER REVISE PLAN OR SEND ME AN EMAIL ADVISING ON
 WHICH PAGE IT CAN BE FOUND.
  
 3) OK
  
 4) 602.1 CONSTRUCTION CLASSIFICATION.
 -WHAT IS THE CONSTRUCTION TYPE FOR THE BUILDING?
 -WHAT IS THE HEIGHT OF ROOF MEMBERS FROM THE FLOOR?
 SEE TABLE 601 FOR CONSTRUCTION TYPES AND APPLICABLE
 EXEMPTIONS.
  
 2ND REVIEW, UNABLE TO LOCATE THIS INFORMATION ON THE
 PLANS.
  
 5) 107.5.3 FBC[AMENDED]PLEASE REVIEW MATERIALS FOR
 CONSTRUCTION TYPE FOR THE GABLE END WALLS AND ADD WHAT
 TYPE OF FINISH MATERIALS ARE BEING USED FOR WEATHER
 PROTECTION. ALSO, TYPE AND VALUE OF INSULATION TO BE
 USED.
  
 2ND REVIEW, A NEW SHEET S-1.0 WAS PROVIDED, OLD PAGE IS
 STILL IN THE PACKAGE. REMOVE ALL SUPERSEDED PAGES, MARK
 VOID, FOLD AND KEEP IN THE SUBMITTAL BUT REMOVED FROM
 THE BOUND SET. ALL PAGES SHOULD BE IN THE ORDER OF THE
 INDEX.
  
 ARCHITECT'S RESPONSE LETTER STATES THAT THIS IS TYPE II
 BUILDING, STRUCTURAL DETAIL SHOWS CDX PLYWOOD
 SHEATHING. FBC B 603, PLEASE CORRELATE.
  
 6) NEW COMMENT - ALL ARCHITECTURAL PAGES HAVE AN IMAGE
 OF THE ARCHITECT'S SIGNATURE. MY UNDERSTANDING IS THAT
 THE BOARD REQUIRES A WET SIGNATURE. EITHER SIGN ALL
 PAGES OR ADVISE VIA EMAIL THAT YOU DISAGREE; AN INQUIRY
 WILL BE SENT TO THE BOARD.
  
 7. NEW COMMENT - THE VALUE APPEARS LOW. PROVIDE AN
 ITEMIZED COST BREAKDOWN INCLUDING QUANTITIES/SF/LF AS
 APPLICABLE.
  
 8) THIS PERMIT WILL BE ISSUED WITH PROVISO:
 SUBMIT PRE-ENGINEERED STEEL TRUSSES TO INSPECTOR PRIOR
 TO INSTALLATION. POINT LOAD OF NEW HANGING FIXTURE TO
 BE INCLUDED IN THE SUBMITTAL.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  