| Date |
Text |
| 2019-07-26 11:46:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE INCORRECT REFERENCES TO THE CURRENT |
| | EDITIONS OF THE FIRE CODES. |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2013 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2013 EDITION. |
| | CONSTRUCTION AND DEMO WORK SHALL COMPLY WITH THE |
| | REQUIREMENTS OF NFPA 241, 2013 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| | |
| | |
| | |
| | 1A) THERE IS AN INDICATION OF NFPA 24, WHICH IS |
| | UNDERGROUND FIRE LINE. |
| | |
| | THE CURRENT EDITION IS 2013. |
| | |
| | IS THERE UNDERGROUND FIRE LINE WORK PROPOSED? |
| | |
| | PLEASE CLARIFY. |
| | |
| | |
| | 1B) THERE IS AN INDICATION OF NFPA 14, WHICH IS FIRE |
| | STANDPIPE. |
| | |
| | THE CURRENT EDITION IS 2013. |
| | |
| | IS THERE STANDPIPE WORK PROPOSED? |
| | |
| | PLEASE CLARIFY. |
| | |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATIONS OF WORK ON THE FIRE |
| | SPRINKLER OR FIRE ALARM SYSTEMS. |
| | |
| | IS THERE FIRE SPRINKLER AND/OR FIRE ALARM EQUIOEMNT |
| | PRESENT AND WILL THEY BE AFFECTED BY THIS PROPOSED |
| | PROJECT? |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | |
| | 3) ANY WORK ON THE FIRE SPRINKLERS OF FIRE ALARM SYSTEM |
| | IT SHALL BE DONE UNDER SEPARAE PERMITS AND SHOP |
| | DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF COMPLIANCE AND |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |