| 2019-08-14 13:40:19 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19071020 |
| | REVIEWED: AUGUST 14, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 107.5.3 FBC[AMENDED]PLEASE REMOVE PLAN SHEETS A-1.0 |
| | TO A-4.1 FROM BOTH SETS AS THESE ARE FOR WORK THAT IS |
| | ISSUED UNDER SEPARATE PERMIT. |
| | |
| | 2) 503.3 FBC[CE] BUILDING ENVELOPE. NEW BUILDING |
| | ENVELOPE ASSEMBLIES THAT ARE PART OF THE ALTERATION |
| | SHALL COMPLY WITH SECTIONS C402.1 THROUGH C402.5. |
| | -PROVIDE INSULATION TYPE AND LOCATION FOR THE NEWLY |
| | CREATED ROOF AREA. |
| | |
| | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS |
| | (P.A.) |
| | - PLEASE PROVIDE 2 COPIES OF ANY P.A.'S. FOR THE |
| | ROOFING, OR INDICATE THAT IT WILL BE DEFERRED UNTIL |
| | ROOFING SUB PERMIT APPLICATION. |
| | |
| | 4) 602.1 CONSTRUCTION CLASSIFICATION. |
| | -WHAT IS THE CONSTRUCTION TYPE FOR THE BUILDING? |
| | -WHAT IS THE HEIGHT OF ROOF MEMBERS FROM THE FLOOR? |
| | SEE TABLE 601 FOR CONSTRUCTION TYPES AND APPLICABLE |
| | EXEMPTIONS. |
| | |
| | 5) 107.5.3 FBC[AMENDED]PLEASE REVIEW MATERIALS FOR |
| | CONSTRUCTION TYPE FOR THE GABLE END WALLS AND ADD WHAT |
| | TYPE OF FINISH MATERIALS ARE BEING USED FOR WEATHER |
| | PROTECTION. ALSO, TYPE AND VALUE OF INSULATION TO BE |
| | USED. |
| | |
| | PROVISO: |
| | SUBMIT PRE-ENGINEERED STEEL TRUSSES TO INSPECTOR PRIOR |
| | TO INSTALLATION. POINT LOAD OF NEW HANGING FIXTURE TO |
| | BE INCLUDED IN THE SUBMITTAL. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |