| 2019-09-23 08:20:46 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | |
| | NEW COMMENTS: |
| | |
| | 3. PANEL B AND PANEL P ARE NOW SHOWN BEING FED FROM A |
| | 100 AMP BREAKER. THE RISER SHOWS THE FEEDER SIZE AS #6 |
| | WIRE, WHICH IS NOT RATED FOR 100 AMPS. PROVIDE |
| | CORRECTION. NEC 310.15(B)(16); FBC RE E3705.1 |
| | 4. RISER SHOWS THE EQUIPMENT GROUNDING CONDUCTOR TO |
| | PANEL B AND PANEL B SIZED AT #10. THIS IS NOT THE |
| | CORRECT SIZE FOR A 100 AMP CIRCUIT. PROVIDE CORRECTION. |
| | NEC 250.122; FBC RE E3704.6, 3607.3.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |