| Date |
Text |
| 2019-08-09 15:14:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. LOAD CALCULATION FOR PANEL B SHOWS DEMAND FACTORS |
| | THAT ARE NOT PERMITTED. BECAUSE THIS IS ONLY A 60 AMP |
| | FEED, DEMAND FACTORS CANNOT BE USED. DEMAND FACTORS ARE |
| | ONLY PERMITTED WHEN THE FEEDERS ARE RATED 100 AMPS OR |
| | MORE. THERFORE, THE CIRCUIT BREAKER FOR THIS WOULD |
| | LIKELY BE OVERLOADED. PROVIDE CORRECTION. NEC 220.82; |
| | FBC RE E3602.2.1 |
| | 2. ORIGINAL RISER DIAGRAM SHOWS A PANEL BEING INSTALLED |
| | FOR THE POOL EQUIPMENT. THIS HAS BEEN REMOVED FROM THIS |
| | DRAWING. WITH THE POOL EQUIPMENT NOW BEING FED FROM |
| | PANEL B, HOW WILL THIS EQUIPMENT HAVE THE REQUIRED |
| | DISCONNECT WITHIN SIGHT OF THE EQUIPMENT? PROVIDE |
| | CLARIFICATION. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |