| 2019-08-24 21:53:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | GUEST HOUSE: |
| | |
| | 1. PROVIDE ACCURATE PANEL SCHEDULES SHOWING OCP, WIRE |
| | SIZE, AND AFCI/GFCI PROTECTION WHERE APPLICABLE. FBC |
| | 107.2.1 NEC 210.8, 210.12 |
| | |
| | 2. SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS |
| | REQUIRED. FBC RE 314&315 |
| | |
| | 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | 4. GARAGE RECEPTACLES MUST BE GFCI PROTECTED NEC 210.8 |
| | |
| | 5. PROVIDE NOTE ON PLAN THAT STATES LOW VOLTAGE AND |
| | GENERATOR REQUIRES SEPARATE ELECTRICAL PERMITS. FBC |
| | 107.2.1 |
| | |
| | 6. SERVICE RECEPTACLES REQUIRED FOR AHU'S AND A/C |
| | CONDENSORS NEC 210.63 |
| | |
| | MAIN HOUSE: |
| | |
| | 1. PROVIDE ACCURATE PANEL SCHEDULES SHOWING OCP, WIRE |
| | SIZE, AND AFCI/GFCI PROTECTION WHERE APPLICABLE. FBC |
| | 107.2.1 NEC 210.8, 210.12 |
| | |
| | 2. PROVIDE LOCATIONS ON PLANS OF ALL PANELS SHOWN ON |
| | ONE-LINE/RISER DIAGRAM. PROVIDE LOCATIONS FOR ALL THREE |
| | ATS'S, ALL SUB-PANELS, AND POOL PANEL. ALL LOCATIONS |
| | NOW SHOWN ON PLAN. FBC 107.2.1 |
| | |
| | 3. SMOKE DETECTORS/ CARBON MONOXIDE DETECTORS REQUIRED |
| | PER FBC RE 314&315. PROVIDE CORRECTION. |
| | |
| | 4. PROVIDE NOTE ON PLAN THAT STATES LOW VOLTAGE AND |
| | GENERATOR REQUIRES SEPARATE ELECTRICAL PERMITS. FBC |
| | 107.2.1 |
| | |
| | 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | 6. LIGHTING PLAN AND POWER PLAN DO NOT HAVE SAME |
| | STRUCTURAL LAYOUT. POWER PLAN SHOWS A ROOM ADJACENT TO |
| | BEDROOM#2 AND BATHROOM #2 BUT IS NOT SHOWN ON LIGHTING |
| | PLAN?? PROVIDE ACCURATE DRAWINGS SHOWING ALL DOOR AND |
| | ROOM LOCATIONS THAT MATCH ON BOTH ELEC AND LIGHTING |
| | PLANS FBC 107.2.1 |
| | |
| | 7. NO ELECTRIC SHOWN FOR A/C CONDENSORS OUTSIDE? FBC |
| | 107.2.1 |
| | |
| | 8. NO LOCATIONS SHOWN FOR AHU'S OR ELECTRIC. FBC |
| | 107.2.1 |
| | |
| | 9. NO ATTIC ACCESS SHOWN? MUST SHOW ATTIC ACCESS WITH |
| | PROPER ELECTRICAL REQUIRED. FBC 107.2.1 |
| | |
| | 10. MUST HAVE BONDING BRIDGE AT SERVICE. NEC 250.94 |
| | |
| | 11. SERVICE RECEPTACLES REQUIRED FOR AHU'S AND A/C |
| | CONDENSORS NEC 210.63 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |