Plan Review Notes
Plan Review Notes For Permit 19070870
Permit Number 19070870
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-05 06:40:508/4/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS NOTE - A COMPREHENSIVE REVIEW COULD NOT BE
 DONE AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED UPON THE RE-REVIEW OF SUBMITTED
 CORRECTIONS.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 2)THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC SEC.109.3
  
 3) INDICATE ON THE PLANS IF THE POOL IS EQUIPPED WITH
 AN AUTO-FILL. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4) ALL GAS AND SPA HEATERS SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82 % FOR HEATERS MANUFACTURED ON OR AFTER
 APRIL 16, 2013, WHEN TESTED IN ACCORDANCE WITH ANSI Z
 21.56. POOL HEATERS FIRED BY NATURAL OR LP GAS SHALL
 NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS. 2017
 FBC-ENERGY ? SEC. R403.10.4
  
 5) HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS. 2017 FBC-
 ENERGY- SEC. R 403.10.3
  
 6) TIME SWITCHES OR OTHER CONTROL METHODS THAT CAN
 AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS
 ACCORDING TO A PRESET SCHEDULE SHALL BE INSTALLED ON
 ALL HEATERS AND PUMPS. HEATERS, PUMPS, AND MOTORS THAT
 HAVE BUILT-IN TIMERS SHALL BE DEEMED IN COMPLIANCE WITH
 THIS REQUIREMENT. 2017 FBC- ENERGY ? SEC. R 403.10.2
  
 7)WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 8) WORK DESCRIPTION SHALL BE FILLED IN ON THE
 ELECTRICAL AND PLUMBING PERMIT APPLICATIONS
  
 9) DESCRIPTION ON PERMIT SHALL STATE POOL RENOVATIONS
  
 10) SEPERATE GAS PERMIT REQUIRED FOR THE GAS POOL
 HEATER
  
 11) VAUUM LINE MISSING ON POOL PLUMBING FLAT DRAWING
  
 12) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATER. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLANS EXAMINER
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695