| Plan Review Notes For Permit 19070860 |
| Permit Number |
19070860 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-06 13:00:46 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) | | | 805-6724 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. FBC B 107.2.1. PLEASE CLARIFY; SCOPE OF WORK ON | | | DRAWINGS INDICATE NEW 1.5 HOUR FIRE RATED DOOR IN | | | SERVICE LOBBY AT 1ST FLOOR THRU 10TH FLOOR, IS THIS A | | | TYPICAL FLOOR PLAN FOR FLOORS ONE THROUGH TEN? IF NOT | | | PROVIDE FOR EACH FLOOR. | | | 2. FBC EB 801.1 & 801.2 LEVEL 2 ALTERATIONS AS | | | DESCRIBED IN SECTION 504 SHALL COMPLY WITH THE | | | REQUIREMENTS OF CHAPTER 8. IN ADDITION TO THE | | | REQUIREMENTS OF THIS CHAPTER, ALL WORK SHALL COMPLY | | | WITH THE REQUIREMENTS OF CHAPTER 7. SUBMITTED DRAWINGS | | | MUST SHOW COMPLIANCE WITH ALL APPLICABLE SECTIONS OF | | | THIS CODE. | | | 3. FBC B 107.2.1 PROVIDE FRAMING DETAILS SUPPLIED FOR | | | ALL NEW WALLS/CEILINGS/INFILL/SOFFITS. SHOW ANCHORAGE, | | | BRACING AND BLOCKING. | | | |
|