 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 16-0330.11 HAS BEEN SUPERSEDED BY MIAMI-DADE COUNTY NOA
 NO. 17-0829.08 AND DOES NOT HAVE AN UL LISTED FIRE
 RATING. PROVIDE TWO SETS OF PRODUCT
 APPROVALS/SPECIFICATIONS FOR THE PROPOSED 1.5-HOUR FIRE
 RATED DOORS TO BE USED.
  