| Plan Review Notes For Permit 19070834 |
| Permit Number |
19070834 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2021-10-21 11:09:53 | SEE COMMENTS FROM 5TH MECH REVIEW. | | | | | | PLAN DENIED | | | 1) PROVIDE GRILL SIZE AND CFM ON ALL SUPPLY GRILLS. | | | SECTION 107 FBC 2019. | | | 2) PROVIDE EQUIPMENT SCHEDULE ON PLAN. | | | PER SECTION 107 FBC 2019. | | | 3) REFER TO SECTION M1602 FBC 2019 | | | RESIDENTIAL CODE RETURN AIR. | | | 4) REFER TO SECTION M1305 APPLIANCE ACCESS | | | 2019 FBC RESIDENTIAL CODE | | | 5) REFER TO SECTION 1401.3 EQUIPMENT SIZING | | | 2019 FBC RESIDENTIAL CODE. | | | 6) PLEASE EXPLAIN WHAT TYPE OF AIR CONDITIONING WORK | | | IS BEING DON ON THE SECOND FLOOR. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 516-805-6732 | | | FAX 561-805-6676 | | | | | | | | | |
|