| 2021-03-24 14:35:31 | 4TH REVIEW FBC-2017 RES. PLUMBING |
| | PERMIT- 19070834 |
| | 3/24/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P-101: THE REVISED PLAN SHOWS AN ELECTRIC TANKLESS |
| | WATER HEATER HOWEVER THE COMMENT RESPONSE LETTER |
| | INDICATES A GAS TANKLESS WATER HEATER WILL BE INSTALLED |
| | USING EXISTING GAS ON SITE. MANUFACTURER?S |
| | SPECIFICATIONS FOR A GAS TANKLESS WATER HEATER HAVE |
| | ALSO BEEN SUBMITTED. IN THE PREVIOUS LETTER DATED |
| | 3/12/2020, IT WAS STATED THAT THERE WAS NO GAS ON SITE |
| | AND GAS REVIEW NOT APPLICABLE. PLEASE CLARIFY ON THE |
| | PLUMBING PLAN WHICH WATER HEATER IS TO BE INSTALLED AND |
| | PROVIDE THE CONDENSATE DISPOSAL PLAN AS PREVIOUSLY |
| | REQUESTED. REFER TO GAS REVIEW COMMENTS FOR GAS WATER |
| | HEATER COMPLIANCE REQUIREMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |