Date Text
2020-06-18 16:39:513RD REVIEW FBC-2017 RES.
 PERMIT- 19070834
 6/18/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW WATER
 HEATER ON THE PLAN- SECTION M2005.1 FBC RES. THIS NEW
 WATER HEATER IS ASSUMED TO BE ELECTRIC-FIRED PER THE
 ARCHITECT'S COMMENT RESPONSES. PROVIDE THE MAKE AND
 MODEL, GALLON CAPACITY, ELECTRICAL DATA, AND EFFICIENCY
 RATING IN THE SCHEDULE- SEE TABLE C404.2 FBC EC FOR
 MINIMUM EFFICIENCY RATING. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE UNIT- SECTION 107.2.1 WPB.
 2) PROVIDE A FRONT ELEVATION VIEW OF THE WATER HEATER
 IN THE CLOSET HOW ACCESS WILL BE PROVIDED, AND THE
 REQUIRED DRAIN PAN AND DRAIN PAN PIPE. SHOW THE DRAIN
 PAN PIPE RUN AND TERMINATION LOCATION- SEE SECTIONS
 P2801.5, P2801.6.1, P2801.6.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  