| Plan Review Notes For Permit 19070834 |
| Permit Number |
19070834 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-10-25 06:32:08 | PLUMBING 2ND REVIEW**DENIED** | | | | | | 1)PROVIDE A SANITARY RISER DRAWING AND NOT A FLAT | | | DRAWING. ALL NEW WORK INCLUDING THE MASTER SHOWER SHALL | | | BE INCLUDED. FBC-PLB 107.3.5 | | | 2) PROVIDE AN EXISTING FLOOR PLAN. SHOW THE LOCATION OF | | | ALL EXISTING PLUMBING FIXTURES INCLUDING THE WATER | | | HEATER. FBC 107.3.5 | | | 3) PROVIDE STEAM UNIT RELIEF, PAN, AND PAN DRAIN | | | DETAIL. FBC 107.2.1 | | | 4) SHT. P102 CALLED THE LOFT PLUMBING DOES NOT SHOW ANY | | | PLUMBING FIXTURES NOR IS THERE A GUT STACK ON THE FLAT | | | DRAWING YOU PROVIDED. PLEASE CLARIFY. FBC 107.2.1 | | | | | | TIM HUNT | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|