2019-10-25 06:32:08PLUMBING 2ND REVIEW**DENIED**
  
 1)PROVIDE A SANITARY RISER DRAWING AND NOT A FLAT
 DRAWING. ALL NEW WORK INCLUDING THE MASTER SHOWER SHALL
 BE INCLUDED. FBC-PLB 107.3.5
 2) PROVIDE AN EXISTING FLOOR PLAN. SHOW THE LOCATION OF
 ALL EXISTING PLUMBING FIXTURES INCLUDING THE WATER
 HEATER. FBC 107.3.5
 3) PROVIDE STEAM UNIT RELIEF, PAN, AND PAN DRAIN
 DETAIL. FBC 107.2.1
 4) SHT. P102 CALLED THE LOFT PLUMBING DOES NOT SHOW ANY
 PLUMBING FIXTURES NOR IS THERE A GUT STACK ON THE FLAT
 DRAWING YOU PROVIDED. PLEASE CLARIFY. FBC 107.2.1
  