Plan Review Notes
Plan Review Notes For Permit 19070834
Permit Number 19070834
Review Stop P
Sequence Number 1
Notes
Date Text
2019-09-06 09:25:20PLUMBING 1ST REVIEW**DENIED**19070834
 1-SUB PLUMBING PERMIT REQUIRED. FBC 105.1
 2-PROVIDE LOCATION ON FLOOR PLAN OF WATER HEATER AND
 PROVIDE INSTALLATION MANUAL SHOWING IT MEETS FLORIDA
 ENERGY CODE. FBC 107.2.1
 3-PROVIDE A COMPLETE SANITARY ISOMETRIC DRAWING. FBC
 107.3.5
 4-PROVIDE SHOWER PAN DETAIL SHOWING THE 2% PRE-PITCH
 AND MATERIAL TO BE USED. FBC 107.2.1
 5-PROVIDE NOTE ON PLAN THE HAMMER ARRESTORS REQUIRED ON
 ALL QUICK CLOSING VALVES. FBC-PLB 604.9 AND WASHING
 MACHINE SHUT OFF VALVES ARE REQUIRED TO BE ACCESSIBLE.
 FBC-PLB606.3
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  