| Permit Number |
19070834 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-09-06 09:25:20 | PLUMBING 1ST REVIEW**DENIED**19070834 | | | 1-SUB PLUMBING PERMIT REQUIRED. FBC 105.1 | | | 2-PROVIDE LOCATION ON FLOOR PLAN OF WATER HEATER AND | | | PROVIDE INSTALLATION MANUAL SHOWING IT MEETS FLORIDA | | | ENERGY CODE. FBC 107.2.1 | | | 3-PROVIDE A COMPLETE SANITARY ISOMETRIC DRAWING. FBC | | | 107.3.5 | | | 4-PROVIDE SHOWER PAN DETAIL SHOWING THE 2% PRE-PITCH | | | AND MATERIAL TO BE USED. FBC 107.2.1 | | | 5-PROVIDE NOTE ON PLAN THE HAMMER ARRESTORS REQUIRED ON | | | ALL QUICK CLOSING VALVES. FBC-PLB 604.9 AND WASHING | | | MACHINE SHUT OFF VALVES ARE REQUIRED TO BE ACCESSIBLE. | | | FBC-PLB606.3 | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|