| 2020-04-07 16:25:38 | REVIEW FBC-2017 MECHANICAL |
| | PERMIT- 19070773 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-401: NOTES 3 & 4 APPEAR TO IDENTIFY THE EF-2 |
| | ON REVISION 8. REVISION 9 HAS THE SAME NOTES 3 & 4 |
| | POINTING AT 2 CIRCLES, PLEASE CLARIFY REVISION 9 |
| | DRAWINGS. FBC WPB 107.2.1 |
| | 2) SHEET M-401: NOTE 19 IS FOR AN EXHAUST FAN IN THE |
| | GENERATOR ROOM, NOTE 1 IS FOR A LOUVER IN THE WALL OF |
| | THE GENERATOR ROOM. THIS LOUVER SHOWS THE AIR BEING |
| | EXHAUSTED OUT. WOULD THIS NOT BE AN INTAKE FOR THE ROOM |
| | AND EXHAUST FAN? FBC WPB 107.2.1 |
| | 3) SHEET M-401: PLEASE SPEC OUT THE LOUVER THAT THE |
| | EXHAUST FAN DUCT (NOTE 20) IS CONNECTED TO. FBC WPB |
| | 107.2.1 |
| | 4) SHEET M-401: NOTES 14 & 15 ARE NEW. PLEASE SUBMIT A |
| | DRAWING SHOWING THIS COMPLETE PIPING SYSTEM INCLUDING |
| | WHERE IT ORIGINATES FROM. FBC WPB 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |
| | |