| 2019-08-09 15:02:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19070773 |
| | 8/9/2019 |
| | |
| | CODES IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M-101, 102, 103, & 104: THERE ARE MISSING |
| | FIRE DAMPERS WHERE DUCTS ARE PENETRATING THE FIRE-RATED |
| | MECHANICAL ROOM/CORRIDOR WALLS. THERE ARE ONLY |
| | MOTORIZED DAMPER SYMBOLS AT THESE LOCATIONS. |
| | 2) M-401: THE GENERATOR ROOM MAKEUP AIR OPENING IS |
| | MISLABELED AS AN EXHAUST OUTLET- SEE NOTE #5. |
| | 3) THE EXHAUST DUCT FROM THE TANK ROOM THAT IS |
| | PENETRATING THE FIRE-RATED GARAGE WALL AND RUNNING |
| | THROUGH THE GARAGE MUST BE HOUSED IN A FIRE- RATED |
| | ENCLOSURE FROM THE POINT OF PENETRATION TO THE OUTLET- |
| | SECTION 510.7.3 FB C M. |
| | |
| | 510.7.3 WALL ASSEMBLIES. |
| | HAZARDOUS EXHAUST DUCT SYSTEMS THAT PENETRATE |
| | FIRE-RESISTANCE-RATED WALL ASSEMBLIES SHALL BE ENCLOSED |
| | IN FIRE-RESISTANCE-RATED CONSTRUCTION FROM THE POINT OF |
| | PENETRATION TO THE OUTLET TERMINAL, EXCEPT WHERE THE |
| | INTERIOR OF THE DUCT IS EQUIPPED WITH AN APPROVED |
| | AUTOMATIC FIRE SUPPRESSION SYSTEM. DUCTS SHALL BE |
| | ENCLOSED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | BUILDING REQUIREMENTS FOR SHAFT CONSTRUCTION AND SUCH |
| | ENCLOSURE SHALL HAVE A MINIMUM FIRE-RESISTANCE RATING |
| | OF NOT LESS THAN THE HIGHEST FIRE-RESISTANCE-RATED WALL |
| | ASSEMBLY PENETRATED |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |