Plan Review Notes
Plan Review Notes For Permit 19070762
Permit Number 19070762
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-01 08:29:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
  
 1. PER WPB FBC 107.2.1 AND 107.3.5.3(12), PROVIDE CODE
 COMPLIANT PLUMBING (SANITARY) RISER DIAGRAM
  
 2. PER WPB FBC 107.2.1, PROVIDE INTERIOR FINISH
 DIMENSIONS OF BATHROOM SHOWING COMPLIANCE WITH FBC RES
 P2705.1, P2708.1 AND P2708.1.1. SPECIFICALLY, THE
 FOLLOWING SHOULD BE MADE CLEAR.
  
 A.A WATER CLOSET, LAVATORY OR BIDET SHALL NOT BE SET
 CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO ANY
 SIDE WALL, PARTITION OR VANITY OR CLOSER THAN 30 INCHES
 (762 MM) CENTER-TO-CENTER BETWEEN ADJACENT FIXTURES.
 THERE SHALL BE A CLEARANCE OF NOT LESS THAN 21 INCHES
 (533 MM) IN FRONT OF A WATER CLOSET, LAVATORY OR BIDET
 TO ANY WALL, FIXTURE OR DOOR.
 B.SHOWER COMPARTMENTS SHALL HAVE NOT LESS THAN 900
 SQUARE INCHES (0.6 M2) OF INTERIOR CROSS-SECTIONAL
 AREA. SHOWER COMPARTMENTS SHALL BE NOT LESS THAN 30
 INCHES (762 MM) IN MINIMUM DIMENSION MEASURED FROM THE
 FINISHED INTERIOR DIMENSION OF THE SHOWER COMPARTMENT,
 EXCLUSIVE OF FIXTURE VALVES, SHOWER HEADS, SOAP DISHES,
 AND SAFETY GRAB BARS OR RAILS.
 C.THE SHOWER COMPARTMENT ACCESS AND EGRESS OPENING
 SHALL HAVE A CLEAR AND UNOBSTRUCTED FINISHED WIDTH OF
 NOT LESS THAN 22 INCHES (559 MM).
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  