| 2019-08-09 16:44:23 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DESIGNER SHALL SIGN PLAN PER FBC 107.2.1. | | | | | | 2. PROVIDE SHOWER PAN DETAIL PER P2709.1 | | | | | | 3. PROVIDE DEMENSIONS OF SHOWER COMPARTMENT PER P2708.1 | | | | | | 4. STATE CFM OF EXHAUST FAN PER R303.3 & M1507. | | | | | | 5. STATE CEILING HEIGHT OF BATHROOM. CEILING HEIGHT | | | SHALL COMPLY WITH R305.1 | | | | | | 6. PROVIDE DEMENSIONS OF BATHROOM FIXTURES. CLEAR SPACE | | | SHALL COMPLY WITH R307.1 | | | | | | 7. STATE CLASSIFICATION OF SHOWER DOOR GLAZING PER | | | TABLE R308.1 (1) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | |
|