Plan Review Notes
Plan Review Notes For Permit 19070762
Permit Number 19070762
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-09 16:44:23BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNER SHALL SIGN PLAN PER FBC 107.2.1.
  
 2. PROVIDE SHOWER PAN DETAIL PER P2709.1
  
 3. PROVIDE DEMENSIONS OF SHOWER COMPARTMENT PER P2708.1
  
 4. STATE CFM OF EXHAUST FAN PER R303.3 & M1507.
  
 5. STATE CEILING HEIGHT OF BATHROOM. CEILING HEIGHT
 SHALL COMPLY WITH R305.1
  
 6. PROVIDE DEMENSIONS OF BATHROOM FIXTURES. CLEAR SPACE
 SHALL COMPLY WITH R307.1
  
 7. STATE CLASSIFICATION OF SHOWER DOOR GLAZING PER
 TABLE R308.1 (1)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  