| Notes |
| Date |
Text |
| 2019-07-29 15:05:27 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. REVISE THE PLAN TO SHOW OCCUPANCY CLASSIFICATION | | | (USE) AND OCCUPANT LOAD FOR THE ROOM WHICH THE DOOR | | | SERVES, FBC B 1010.1.10. IT IS NOT CLEAR IF PANIC BARS | | | ARE REQUIRED. | | | | | | 2. I WAS UNABLE TO LOCATE AN ADA THRESHOLD DETAIL IN | | | THE PRODUCT APPROVAL. PLEASE INDICATE, PROVIDE A | | | PRODUCT APPROVAL WHICH INCLUDES THIS AS AN OPTION AND | | | INDICATE, OR PROVIDE INFORMATION AS TO WHY THIS IS NOT | | | APPLICABLE, FBC A 403.1, 303.3. | | | | | | 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | | | | |
|