| Date |
Text |
| 2019-07-22 10:56:15 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE APPLICATION INDICATES "CONSTRUCTION TRAILER |
| | TEMPORARY FENCE" |
| | |
| | THERE IS NO CLEAR INDICATION OF THE LOCATION OF THE |
| | TRAILER. |
| | |
| | PLEASE REVIEW AND CLARFY THE INTENT OF THE APPLICATION; |
| | IF FOR A TRAILER AND FENCE, PLEASE PROVIDE EXACT |
| | LOCATION OF THE CONSTRUCTION TRAILER WITH DIMENSIONS TO |
| | PROPERTY LINES, NEIGHBOR BUILDINGS, PROPOSED BUILDING, |
| | ETC. |
| | |
| | |
| | |
| | 2) THERE IS A GATE INDICATED IN THE MIDDLE OF THE |
| | VACANT FIELD. THERE IS NO FD ACCESS ROAD INTO THE |
| | PROPSED FENCED SITE. |
| | |
| | PER NFPA 1 |
| | |
| | 18.2.3 FIRE DEPARTMENT ACCESS ROADS. |
| | 18.2.3.1 REQUIRED ACCESS. |
| | 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL |
| | BE PROVIDED |
| | FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING |
| | HEREAFTER |
| | CONSTRUCTED OR RELOCATED. |
| | 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST |
| | OF ROADWAYS, FIRE |
| | LANES, PARKING LOT LANES, OR A COMBINATION THEREOF. |
| | |
| | 18.2.3.4.1 DIMENSIONS. |
| | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED |
| | WIDTH OF NOT LESS THAN 20 FT (6.1 M). |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) THERE ARE NO DIMENSIONS INDICATED FOR THE GATE. |
| | |
| | 18.2.3.4.1 DIMENSIONS. |
| | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED |
| | WIDTH OF NOT LESS THAN 20 FT (6.1 M). |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 4) KNOX PADLOCKS ARE RECOMMENDED FOR EACH TO BE USED IN |
| | CONJUCTION WITH YOUR LOCKS SO YOUR LOCK OR CHAIN WILL |
| | NOT BE CUT IN THE EVENT OF NEEDED EMERGENCY INCIDENT |
| | ACCESS. |
| | |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |