| Date |
Text |
| 2019-07-18 15:02:06 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) THE GATES INDICATED ARE REQUIRED TO BE 20' FOR FIRE |
| | DEPARTMENT ACCESS IN THE EVENT OF EMERGENCY. |
| | |
| | PER NFPA 1 |
| | |
| | 18.2.3.4.1 DIMENSIONS. |
| | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED |
| | WIDTH OF NOT LESS THAN 20 FT ( |
| | |
| | AND |
| | |
| | NFPA 241 |
| | |
| | 7.5.5 ACCESS ROADWAYS. |
| | 7.5.5.1 EVERY BUILDING SHALL BE ACCESSIBLE BY FIRE |
| | DEPARTMENT |
| | APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER |
| | DRIVING |
| | SURFACE OF NOT LESS THAN 6.1 M (20 FT) OF UNOBSTRUCTED |
| | WIDTH, HAVING |
| | THE ABILITY TO WITHSTAND THE LIVE LOADS OF FIRE |
| | APPARATUS, AND |
| | HAVING A MINIMUM OF 4.1 M (13 FT 6 IN.) OF VERTICAL |
| | CLEARANCE. |
| | 7.5.5.2 ACCESS FOR USE OF FIRE DEPARTMENT APPARATUS |
| | SHALL BE |
| | PROVIDED TO THE IMMEDIATE JOB SITE AT THE START OF THE |
| | PROJECT |
| | AND MAINTAINED UNTIL COMPLETION. |
| | |
| | PLEASE ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 2) IT IS STRONGLY RECOMMENDED, NOT REQUIRED, THAT A |
| | KNOX PADLOCK BE PROVIDED FOR 24HR EMERGENCY ACCESS. |
| | |
| | THE KNOX PADLOCK CAN BE USED IN COMBINATION WITH YOUR |
| | PADLOCK FOR ACCESS AND SECURITY WHEN THE INCIDENT IS |
| | COMPLETE. |
| | |
| | WEST PALM BEACH FIRE RESCUE KNOX PADLOCKS CAN BE |
| | PURCHASED AT HTTPS://WWW.KNOXBOX.COM/ |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |