| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1.FBC B 107.2.1. PLEASE CORRECT THE FOLLOWING; ON THE |
| | SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR |
| | ASSEMBLIES: COLUMN HEADING ?SHUTTER SPAN?; SEE TYPICAL |
| | (1) HV BLADE SHUTTER ELEVATION; SHEET 5 OF PRODUCT |
| | APPROVAL FL1850. COLUMN HEADING ?ANCHOR SPACING?; |
| | PROVIDE INFORMATION FROM PAGE 12 OF PRODUCT APPROVAL |
| | FL1850 TAPCON W/ADVANCED THREADFORM TECHNOLOGY REQUIRES |
| | A .9 FACTOR... COLUMN HEADING ?SHUTTER INSTALLED |
| | VERTICAL/HORIZONTAL?: ACCORDION SHUTTERS ARE INSTALLED |
| | VERTICALLY AS PER PRODUCT APPROVAL FL1580. |
| | 2. FBC B 107.2.1. PLEASE VERIFY THE INFORMATION ON THE |
| | SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR |
| | ASSEMBLIES FOR PRODUCT APPROVAL FL11291. EXAMPLE: PAGE |
| | 13 TABLE 4 CONCRETE ?? & 5/16? ELCO ULTRACON SPANS |
| | 16?-0 < 16?-6? 40 (PSF) ANCHOR SPACING IS 9.0?. PLEASE |
| | NOTE SCREEN PANELS CAN BE MOUNTED VERTICALLY OR |
| | HORIZONTAL. PLEASE USED APPROPRIATE INSTALLATION METHOD |
| | AND SPAN. |
| | |