Plan Review Notes
Plan Review Notes For Permit 19070718
Permit Number 19070718
Review Stop P
Sequence Number 2
Notes
Date Text
2019-08-29 13:27:211) SHT.A-2 SHOWS A COUNTER WITH BAR STOOLS. SHOW ON THE
 PLAN WHAT THIS AREA IS BEING USED FOR. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) TEMPERED WATER WILL BE REQUIRED AT THE TOILET ROOM
 LAVATORY PER 2017 FBC -PLUMBING SEC.416.5.
 3) THE BAR SINK IS BEING USED AS A BREAK ROOM SINK IT
 SHALL BE INSTALLED IN COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY SEC.212 & SECS.606.2, 606.3,
 606.4,606.5. PROVIDE AN ELEVATION DETAIL OF THE SINK
 /CABINET AND SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE
 ARCHITECTURAL PLAN.
 4) DUE TO THE OCCUPANT LOAD OF 27.27 PERSONS, A TOTAL
 OF 2 TOILET ROOMS ARE REQUIRED PER THE 2017
 FBC-PLUMBING SEC.403.2 AND TABLE 403.1.THE TOILET ROOM
 SHALL FULLY COMPLY WITH THE FBC-ACCESSIBILITY CODE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  