| 2019-07-31 08:06:52 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19070718 |
| | REVIEWED: JULY 31, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 107.2.5 FBC[AMENDED] DEMOLITION PLAN. |
| | - PROVIDE DEMOLITION PLAN TO SHOW EXISTING |
| | CONFIGURATION, AREA AND DIMENSIONS. |
| | |
| | 2) 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH |
| | CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN |
| | ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL |
| | COST OF WORK. |
| | - PLEASE INCLUDE ALL SUB CONTRACTORS, MILLWORK AND |
| | FINISH WORK . |
| | |
| | 3) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| | CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| | EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| | LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| | BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3 |
| | SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER. |
| | A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE |
| | METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF |
| | OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN |
| | BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION |
| | CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE |
| | REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE |
| | SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS |
| | OF THIS CODE. |
| | C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF |
| | THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | - WHICH METHOD IS BEING USED FOR COMPLIANCE? |
| | (PRESCRIPTIVE,WORK AREA OR PERFORMANCE) |
| | |
| | 4) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED. |
| | A) LEVEL 1 ALTERARTION |
| | B) LEVEL 2 ALTERARTION |
| | C) LEVEL 3 ALTERARTION |
| | - PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA IF |
| | USING COMPLIANCE METHOD. |
| | |
| | 5) 1004.1 FBC[B]LIFE SAFETY DATA |
| | - PLEASE PROVIDE THE OCCUPANT LOAD, COMMON PATH OF |
| | TRAVEL AND EXIT(S) FOR EGRESS. |
| | |
| | 6) 107.5.3 FBC[AMENDED]PROVIDE PROJECT DATA. |
| | - AREA OF WORK BEING PERFORMED |
| | |
| | 7) 107.5.3 FBC[AMENDED] IS THE BUILDING SPRINKLERED OR |
| | NON SPRINKLERED? |
| | |
| | 8) 202.3 FBC[A] ALTERATIONS. WHERE EXISTING ELEMENTS OR |
| | SPACES OR COMMON AREAS ARE ALTERED, EACH ALTERED |
| | ELEMENT, SPACE OR AREA SHALL COMPLY WITH THE APPLICABLE |
| | REQUIREMENTS OF CHAPTER 2 AND SECTION 201.1.1. SEE |
| | SECTION 208.1 FOR EXISTING PARKING. EXCEPTIONS: |
| | -405.2 AND 405.7 FBC[A]THE RAMP AT MAIN ENTRY DOES NOT |
| | MEET THE REQUIREMENTS FOR LANDINGS AT THE TOP AND |
| | BOTTOM. OF A RAMP. PLEASE ADJUST THE RAMP TO HAVE |
| | LANDING AT THE DOORS AND THE LANDING CAN DOUBLE AS |
| | CLEAR SPACE AT THE DOORS. |
| | -ADD SLOPE TO THE RAMP. |
| | -CHANGE IN ELEVATION AND DIMENSION. |
| | - SHOW LANDING OUTSIDE ENTRY DOOR WITH SLOPE TO MEET |
| | ACCESSIBILITY 405.7. |
| | |
| | 9) 227 AND 904 FBC[A]SERVICE COUNTER. |
| | - PLEASE SHOW DETAILS OF MILLWORK AND HOW IT MEETS THE |
| | REQUIREMENTS FOR COMPLIANCE WITH ACCESSIBILITY CODE. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |