2019-07-31 08:06:52BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19070718
 REVIEWED: JULY 31, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.2.5 FBC[AMENDED] DEMOLITION PLAN.
 - PROVIDE DEMOLITION PLAN TO SHOW EXISTING
 CONFIGURATION, AREA AND DIMENSIONS.
  
 2) 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH
 CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN
 ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL
 COST OF WORK.
 - PLEASE INCLUDE ALL SUB CONTRACTORS, MILLWORK AND
 FINISH WORK .
  
 3) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
 A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE
 METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
 C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 4) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
 A) LEVEL 1 ALTERARTION
 B) LEVEL 2 ALTERARTION
 C) LEVEL 3 ALTERARTION
 - PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA IF
 USING COMPLIANCE METHOD.
  
 5) 1004.1 FBC[B]LIFE SAFETY DATA
 - PLEASE PROVIDE THE OCCUPANT LOAD, COMMON PATH OF
 TRAVEL AND EXIT(S) FOR EGRESS.
  
 6) 107.5.3 FBC[AMENDED]PROVIDE PROJECT DATA.
 - AREA OF WORK BEING PERFORMED
  
 7) 107.5.3 FBC[AMENDED] IS THE BUILDING SPRINKLERED OR
 NON SPRINKLERED?
  
 8) 202.3 FBC[A] ALTERATIONS. WHERE EXISTING ELEMENTS OR
 SPACES OR COMMON AREAS ARE ALTERED, EACH ALTERED
 ELEMENT, SPACE OR AREA SHALL COMPLY WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTER 2 AND SECTION 201.1.1. SEE
 SECTION 208.1 FOR EXISTING PARKING. EXCEPTIONS:
 -405.2 AND 405.7 FBC[A]THE RAMP AT MAIN ENTRY DOES NOT
 MEET THE REQUIREMENTS FOR LANDINGS AT THE TOP AND
 BOTTOM. OF A RAMP. PLEASE ADJUST THE RAMP TO HAVE
 LANDING AT THE DOORS AND THE LANDING CAN DOUBLE AS
 CLEAR SPACE AT THE DOORS.
 -ADD SLOPE TO THE RAMP.
 -CHANGE IN ELEVATION AND DIMENSION.
 - SHOW LANDING OUTSIDE ENTRY DOOR WITH SLOPE TO MEET
 ACCESSIBILITY 405.7.
  
 9) 227 AND 904 FBC[A]SERVICE COUNTER.
 - PLEASE SHOW DETAILS OF MILLWORK AND HOW IT MEETS THE
 REQUIREMENTS FOR COMPLIANCE WITH ACCESSIBILITY CODE.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  