| 2019-07-26 10:42:58 | 1ST REVIEW: 19070700 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW DIMENSIONS AND LABEL CLEAR FLOOR SPACE FOR THE |
| | TOILET. PER FBC ACC 604.3.1 |
| | |
| | 2. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM |
| | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET |
| | OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR. PER FBC ACC |
| | 604.7 |
| | |
| | 3. SHOW COMPLIANCE FOR LAVATORY IN THE ACCESSIBLE STALL |
| | HEIGHT OF THE RIM AND KNEE AND TOE CLEARANCE. FBC ACC |
| | 606.2, 606.3 |
| | |
| | 4. GRAB BARS SHALL BE MEASURED FROM FINISH FLOOR TO THE |
| | TOP OF THE GRIPPING SURFACE AT 33" MIN- 36" MAX. PER |
| | FBC ACC 609.4 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |