| Plan Review Notes For Permit 19070669 |
| Permit Number |
19070669 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-24 15:42:21 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | MAIN TO DOCK TO MEET 555.3 GFCI PROTECTION | | | REQUIREMENTS. | | | | | | FAULT CURRENT CALCULATION REQUIRED FOR THE SERVICE. | | | 110.9, 10 | | | | | | MAIN FEEDING DOCK IS 150A WITH #6 WIRE??? | | | | | | PVC ON UNDERSIDE OF DOCK WILL HAVE TO MEET 352.44 | | | EXPANSION FITTING REQUIREMENTS. | | | | | | CONNECTIONS ON DOCK SHALL MEET 555.9 | | | | | | TRANSFORMER AND SERVICE TO MEET 555.5 , AND 555.7 |
|