| Plan Review Notes For Permit 19070664 |
| Permit Number |
19070664 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-09-24 13:23:12 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | THIS REVIEW CAN NOT PASS UNTIL PERMIT NUMBER 19060008 | | | (RAMP) IS APPROVED. THE RAMP PERMIT STILL HAS PENDING | | | COMMENTS FROM PRIOR REVIEW THAT HAVE NOT BEEN | | | ADDRESSED. |
|