| 2019-08-12 13:10:34 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO REVISIONS ARE INDICATED ON PLAN SHEET. THE ONLY |
| | CHANGE I CAN SEE IS THAT THE METER CAN IS SHOWN INSIDE |
| | THE HALLWAY, WHICH IS OBVIOUSLY NOT CORRECT. PROVIDE |
| | NARRATIVE OF CHANGES AND CLOUD CHANGES ON PLAN. CORRECT |
| | THE LOCATION OF METER CAN ON PLAN. WPB FBC 107.2.1 |
| | 2. AS A PROVISO ON THE ORIGINAL PLAN, IT WAS NOTED THAT |
| | THE OUTSIDE DISCONNECT MUST BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT, WHICH IN A LETTER FROM FPL WAS STATED AS |
| | 21110 AIC. THE DISCONNECT ON THIS PLAN STILL SHOWS A |
| | RATING OF 10,000 AIC. PROVIDE CORRECTION. NEC 110.9, |
| | 110.10; FBC RE E3606.3 |
| | 3. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN |
| | EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE |
| | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 |
| | 4. LOAD CALCULATION STATES THIS IS A 125 AMP SERVICE. |
| | RISER DIAGRAM INDICATES THIS IS A 100 AMP SERVICE. |
| | CORRECT DISCREPANCY. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |