| Date |
Text |
| 2020-07-01 16:02:33 | INSUFFICIENT |
| | |
| | PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE |
| | DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401 |
| | OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE |
| | COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION. |
| | THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO |
| | REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF |
| | HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS, |
| | THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION, |
| | NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE |
| | APPROVED. |
| | |
| | 1) UPDATED COMMENT: SURVEY OF UNDERGROUND FACILITIES - |
| | THE BASE OF THE POLE IS BEING INSTALLED UNDERGROUND SO |
| | THIS IS REQUIRED. |
| | |
| | A. THE SURVEY THAT WAS PROVIDED WITH THE APPLICATION |
| | DOES NOT SHOW THE LOCATION OF THE UNDERGROUND UTILITY |
| | FACILITIES THAT ARE INCLUDED ON THE ENGINEERING PLANS |
| | (IT SPECIFICALLY STATES THAT UNDERGROUND UTILITIES AND |
| | IMPROVEMENTS WERE NOT LOCATED IN NOTE #3). THE PROPOSED |
| | POLE HAS A 10 FOOT DEEP UNDERGROUND BURIAL. THE |
| | INFORMATION HAS NOT BEEN PROVIDED THAT THIS WILL NOT |
| | IMPACT EXISTING UTILITIES (ALL OF WHICH ARE SHOWN LESS |
| | THAN 10 FEET IN DEPTH). THE CROSS SECTION PLANS NEED TO |
| | SHOW THE POLE FOUNDATION. POT HOLES ARE REQUIRED IF |
| | PROPOSED POLE IS WITHIN TEN FEET OF EXISTING WATER, |
| | SEWER OR STORM WATER FACILITIES. |
| | |
| | B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS |
| | SURVEY INFORMATION. |
| | |
| | 2) PUBLIC UTILITY LETTERS, TELEPHONE, NATURAL GAS, |
| | ELECTRIC SERVICE, AND TELEVISION CABLE - PUBLIC UTILITY |
| | LETTERS NEED TO BE PROVIDED BY ANY PROVIDER WITHIN FIVE |
| | (5) FEET OF THE PROPOSED POLE (AND THE BORE AND BORE |
| | PITS IF INCLUDED ON THIS APPLICATION). PLEASE NOTE THAT |
| | AS STATED PREVIOUSLY, THE UNDERGROUND INFORMATION WAS |
| | NOT PROVIDED ON THE SURVEY. THE ENGINEERING PLAN STATES |
| | THAT THE CONTRACTOR IS TO FIELD VERIFY UNDERGROUND |
| | UTILITIES; HOWEVER, THE CITY CODE REQUIRES THAT THIS BE |
| | PROVIDED PRIOR TO THE CITY APPROVAL. IF THERE ARE NO |
| | UNDERGROUND UTILITIES IN THE AREA, THIS NEEDS TO BE |
| | CLEARLY STATED ON THE PLANS AND HOW THIS INFORMATION |
| | WAS DETERMINED. |
| | |
| | 3) THE OVERALL HEIGHT OF THE POLE AND ANTENNA IS SHOWN |
| | AS 32 FEET ON SHEET C3 ELEVATION & EQUIPMENT PLAN AND |
| | 38 FEET 1 INCH ON SHEET S1 ASSEMBLY ELEVATIONS. BOTH |
| | PLANS NEED TO SHOW THE SAME, ACCURATE HEIGHT. |
| | |
| | 4) PLEASE NOTE THAT THE N/S/E/W DIRECTIONS ON THE |
| | EXISTING CONDITIONS PHOTOS ARE MISLABELED. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |