| Plan Review Notes For Permit 19070625 |
| Permit Number |
19070625 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-09-23 17:09:17 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19070625 | | | 9/23/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1.1: PLEASE IDENTIFY ALL NEW ROOMS ON THE | | | PLAN- SECTION 107.2.1 WPB. | | | | | | 2) M1.1: : REFER TO SECTION 809.2 FBC-EX AND PROVIDE | | | MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND | | | SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A | | | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS | | | OF OUTDOOR AIR. | | | | | | 3) M1.1: THERE IS A MISSING FIRE DAMPER WHERE THE 18/10 | | | DUCT IS PENETRATING THE FIRE-RATED WALL ABOVE DOOR 01- | | | SECTION 607.5.2 FBC M | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|