| Date |
Text |
| 2019-07-30 15:53:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 2. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| | SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC |
| | 410.10(D); FBC RE E4003.11 |
| | 3. NOTE 27 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE E4002.14 |
| | 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE E3902.16 |
| | 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| | OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 7. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN |
| | KITCHEN, INCLUDING THE ISLAND, REQUIRE GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6 |
| | 8. DETAIL FOR DISHWASHER / DISPOSAL DOES NOT PERMIT FOR |
| | GFCI PROTECTION OF DISHWASHER. PROVIDE GFCI PROTECTION |
| | FOR DISHWASHER. NEC 210.8(D); FBC RE E3902.10 |
| | 9. RECEPTACLE OUTLETS IN BATHROOMS REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE |
| | E3902.1 |
| | 10. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 11. PLAN DOES NOT SHOW LOCATION OF PANEL B. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 12. PLAN DOES NOT SHOW LOCATION OF LAUNDRY CIRCUITS |
| | SHOWN IN PANEL SCHEDULEL. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 13. PLAN SHOWS WHAT APPEARS TO BE STANDARD RECESS |
| | LIGHTS IN CLOSET. PER CODE, LIGHTING WITH OPEN OR |
| | PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR |
| | LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. |
| | PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 |
| | 14. PLAN DOES NOT SHOW LOCATION OF AC EQUIPMENT. |
| | PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING |
| | OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER |
| | CODE. NEC 210.63; FBC RE E3901.12 |
| | 15. RECEPTACLES INSTALLED OUTDOORS REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE |
| | E3902.3 |
| | 16. RISER DIAGRAM DOES NOT PROVIDE WIRE SIZE TO MDP |
| | FROM METER. PROVIDE CORRECTION. WPB FBC 107.2.1 |
| | 17. RISER DIAGRAM SHOWS 4 CONDUCTORS AND AN EQUIPMENT |
| | GROUND TO SUB-PANELS. IS THIS A 3 PHASE SYSTEM? LOAD |
| | CALCULATION AND PANEL SCHEDULES SHOW A SINGLE PHASE |
| | SERVICE. CORRECT DISCREPANCY. WPB FBC 107.2.1; NEC |
| | 215.5 |
| | 18. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| | BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| | FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| | R314.3(4), NFPA 72:29.8.3.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |