| 2019-08-07 10:31:59 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| | FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC |
| | 225.30 |
| | 2. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, PROVIDE |
| | LOCATION OF PANEL TO CONFIRM CODE COMPLIANCE. PROVIDE |
| | PANEL SCHEDULE. NEC 210.8, 210.12, 210.19, 210.20, |
| | 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | 3. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, PROVIDE |
| | GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A BUILDING |
| | OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH CIRCUIT. |
| | NEC 250.32; FBC RE3607.3 |
| | 4. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, FEEDERS |
| | THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THIS PANEL. NEC 225.31, 225.32 |
| | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | 6. LOAD SCHEDULE INDICATES THAT THE BATHROOM RECEPTACLE |
| | WILL BE ON A 15 AMP CIRCUIT. A MINIMUM OF ONE 20 AMPERE |
| | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| | RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| | OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE |
| | E3703.4 |
| | 7. SHOW LOCATION OF MINI-SPLIT UNIT ON ELECTRICAL PLAN. |
| | PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING |
| | OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER |
| | CODE. NEC 210.63; FBC RE E3901.12 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |