Plan Review Notes For Permit 19070552
Permit Number 19070552
Review Stop E
Sequence Number 1
Notes
Date Text
2019-08-07 10:31:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC
 225.30
 2. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, PROVIDE
 LOCATION OF PANEL TO CONFIRM CODE COMPLIANCE. PROVIDE
 PANEL SCHEDULE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 3. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, PROVIDE
 GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A BUILDING
 OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH CIRCUIT.
 NEC 250.32; FBC RE3607.3
 4. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, FEEDERS
 THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THIS PANEL. NEC 225.31, 225.32
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 6. LOAD SCHEDULE INDICATES THAT THE BATHROOM RECEPTACLE
 WILL BE ON A 15 AMP CIRCUIT. A MINIMUM OF ONE 20 AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE
 E3703.4
 7. SHOW LOCATION OF MINI-SPLIT UNIT ON ELECTRICAL PLAN.
 PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING
 OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER
 CODE. NEC 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved