| 2019-08-20 10:32:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54= NATIONAL FUEL GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | 1. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR SIZING |
| | OF THE STORM DRAIN PIPING SHOWING COMPLIANCE WITH FBC |
| | PL 1106.1, 1106.2 AND 1106.3. |
| | 2. TO SHOW COMPLIANCE WITH FBC PL 1101.7, INDICATE THE |
| | MAXIMUM DEPTH OF POTENTIAL PONDING FOR WHICH THE ROOF |
| | IS DESIGNED AND SHOW THE MAXIMUM VERTICAL DISTANCE |
| | BETWEEN THE HIGH POINT OF THE ROOF PERIMETER AND THE |
| | RIM OF THE ROOF DRAIN INLET. ADDITIONALLY, IF THE |
| | PHYSICAL DISTANCE EXCEEDS THE ALLOWABLE DISTANCE, THEN |
| | PROVIDE A SECONDARY ROOF DRAIN SYSTEM TO COMPLY WITH |
| | THE PROVISION OF FBC PL 1108. |
| | 3. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATION SHEET AND INSTALLATION |
| | PROCEDURES/RECOMMENDATIONS. PROVIDE FOR A MODIFIED |
| | GRANULAR SUB BASE LAYER TO ALLOW PROPER DIFFUSION OF |
| | RAINWATER INTO THE GROUND. DETAIL ON P1.0 SHALL REFLECT |
| | THE MANUFACTURER?S PRODUCT AND RECOMMENDATIONS AND THE |
| | SUB BASE LAYER. |
| | 4.PPER WPB FBC 107.2.1, REGARDING THE NYOPLAST/ADS |
| | GRATE SPECIFICATIONS ON P1.0, PLEASE MATCH TO STRUCTURE |
| | AND SPECIFY WHICH GRATE IS REQUIRED. |
| | 5. PER WPB FBC 107.1.2, PLEASE PROVIDE ON SITE PLAN THE |
| | HORIZONTAL UNOBSTRUCTED DISTANCE FROM THE NEW STRUCTURE |
| | TO THE NEAREST TOILET FACILITIES. PROVIDE CALCULATIONS |
| | FOR OCCUPANCY FOR THE SITE AND SHOW MINIMUM PLUMBING |
| | FIXTURE REQUIREMENTS FOR SITE PER FBC PL 403 AND ACTUAL |
| | PLUMBING FIXTURE COUNT FOR THE SITE. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19070532 5601 GREENWOOD AVE |
| | |