| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. MODULAR DESIGN PLANS PROVIDED STATE THAT THERE ARE 2 |
| | ELECTRICAL PANELS. THE LOAD CALCULATION SHOWN ON THESE |
| | PLANS IS 97 AMPS FOR PANEL A, AND 65 AMPS FOR PANEL B. |
| | THE LOAD CALCULATION PROVIDED ON THE RISER DIAGRAM DOES |
| | NOT MATCH THIS. PROVIDE CLARIFICATIONS AND CORRECTIONS. |
| | NEC 220. |
| | 2. BASED ON LOAD CALCULATIONS, THE PROPOSED 100 AMP |
| | SERVICE IS NOT ADEQUATE TO SUPPLY THE LOAD. PROVIDE |
| | CORRECTION. NEC 215.2, 220 |
| | 3. A MAIN BREAKER IS REQUIRED AT THE SERVICE LOCATION. |
| | RISER PROVIDED SHOWS A 100 AMP METER CAN FEEDING #6 |
| | WIRES WITH NO OVER CURRENT PROTECTION. THIS WIRE IS NOT |
| | RATED FOR 100 AMPS. THE SERVICE DOES NOT SHOW THE |
| | REQUIRED MAIN BREAKER. PROVIDE CORRECTION. NEC 230.70, |
| | 310.15(B)(16) |
| | 4. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET |
| | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE |
| | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. THIS PERSON MUST BE A LICENSED DESIGN |
| | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. |
| | PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |