| Plan Review Notes For Permit 19070527 |
| Permit Number |
19070527 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-19 18:31:10 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE WIND VELOCITY ON DRAWING NUMBER SD-2 IS | | | SPECIFIED AS 105 MPH FOR RISK CATEGORY II. THIS PROJECT | | | HAS A VULT WINDSPEED OF 170 MPH (132 MPH VASD) FOR RISK | | | CATEGORY II. AWNINGS ARE TYPICALLY CONSIDERED AS RISK | | | CATEGORY I. THE CATEGORY I WINDSPEED FOR THIS PROJECT | | | IS 155 MPH VULT (120 MPH VASD). THE WINDSPEED AND/OR | | | RISK CATEGORY NEED TO BE CORRECTED. FBC 1609.3 AND | | | 1609.3.1 | | | |
|