| Plan Review Notes For Permit 19070498 |
| Permit Number |
19070498 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-16 12:41:37 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. A CORPORATION CANNOT OBTAIN AN OWNER/BUILDER PERMIT | | | PER ATTORNEY GENERAL, FS489. A CONTRACTOR IS REQUIRED. | | | | | | 2. FBC 109, VALUE IS TO INCLUDE ALL LABOR AND | | | MATERIALS. VALUE IS TOO LOW. | | | | | | 3. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER | | | SHEET WHICH SHOWS THE STATUS AND PRODUCT APPROVAL | | | NUMBER, FBC R 301. | | | | | | 4. REVISE PLAN TO SHOW WINDOW SIZES, FBC R 301. | | | | | | 5. NON IMPACT WINDOW PRODUCT APPROVAL WAS PROVIDED; | | | PROVIDE CALCULATIONS FOR AGGREGATE GLAZED AREA TO SHOW | | | THAT IT MEETS THE EXCEPTION FBC EB 707.4(1) OR PROVIDE | | | IMPACT PROTECTION. | | | |
|