Date Text
2019-08-13 12:02:24ODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. DISHWASHER
  
 A. P1.1.2/P2.1.1/A1.1.1
  
 1)PLUMBING DRAWINGS INDICATE THE DISHWASHER IS LOCATED
 UNDER THE ISLAND BAR/COUNTER. ARCHITECTURAL DRAWING
 A1.1.1 SHOWS THE DISHWASHER ADJACENT TO THE SINK.
 P1.1.2 SANITARY ISO AND FLOOR PLAN SHOW DISHWASHER
 DISCHARGING TO A FLOOR SINK. P2.1.1 PLUMBING FIXTURE
 CONNECTION SCHEDULE CALLS TO COMPLY WITH FBC PL 802.1.6
 OR 802.1.7. PLEASE NOTE THAT IF DISCHARGING TO A FLOOR
 SINK PER 802.1.7, THAT THE FLOOR SINK SHALL NOT BE
 INSTALLED IN A CONCEALED PLACE BUT MUST HAVE READY
 ACCESS PER FBC PL 802.3. COMPLIANCE WITH FBC PL 802.1.6
 ALLOWS FOR A SIMPLE UNDER THE COUNTER CONNECTION TO THE
 SINK WASTE SO LONG AS THE DISHWASHER IS ADJACENT TO THE
 SINK AS NOTED ON A1.1.1 AND THE REQUIREMENTS OF 802.1.6
 ARE MET. PER WPB FBC 107.2.1, PLEASE CLARIFY WHICH
 INDIRECT WASTE METHOD IS TO BE USED ON BOTH THE
 SCHEDULE AND THE SANITARY PIPING DRAWINGS AS WELL AS
 THE ACTUAL LOCATION OF THE DISHWASHER.
  
  
 2. ICEMAKER
  
 A. PER FBC PL 608.2 AND 608.3, PROVIDE A BACKFLOW
 PREVENTER IN THE WATER SUPPLY TO THE ICE MAKER AND
 INDICATE ON THE WATER RISER AND SPECIFY IN THE PLUMBING
 FIXTURE CONNECTION SCHEDULE.
  
  
 3. RE: P2.1.1
  
 A.GENERAL PLUMBING NOTES
  
 1) DOMESTIC WATER PIPING NOTE 4; AMEND NOTE TO READ
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010 AND
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED AND WHERE SHOWN ON THE WATER RISER DIAGRAM.
 2) DOMESTIC WATER PIPING NOTE 13 CALLS FOR A PRESSURE
 AND TEMPERATURE RELIEF VALVE FOR ALL WATER HEATERS
 (TANK-TYPE AND TANKLESS) AND AN EXPANSION TANK AS
 REQUIRED. PER WPB FBC107.2.1, CLARIFY WHETHER OR NOT
 ONE OR BOTH OF THESE ITEMS ARE REQUIRED FOR THE
 SCHEDULED TANKLESS WATER HEATER(S) AND IF THEY ARE
 REQUIRED THEN INCLUDE THEM IN THE ELECTRIC TANKLESS
 WATER HEATER DETAIL. ADDITIONALLY, IF THE RELIEF VALVE
 IS REQUIRED THEN PROVIDE FOR THE DISCHARGE OF SAID
 VALVE IN ACCORDANCE WITH FBC PL 504.6.
 3) DO YOU REQUIRE AN EMERGENCY PAN FOR THE TANKLESS
 WATER HEATER AS STATED IN NOTE 12? IF SO THEN PROVIDE A
 DETAIL SHOWING COMPLIANCE WITH FBC PL 504.7.1 AND
 504.7.2. IF NOT THEN REMOVE THE NOTE.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19070494 1921 S DIXIE HWY
  