| Date |
Text |
| 2019-08-13 12:02:24 | ODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54= STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. DISHWASHER |
| | |
| | A. P1.1.2/P2.1.1/A1.1.1 |
| | |
| | 1)PLUMBING DRAWINGS INDICATE THE DISHWASHER IS LOCATED |
| | UNDER THE ISLAND BAR/COUNTER. ARCHITECTURAL DRAWING |
| | A1.1.1 SHOWS THE DISHWASHER ADJACENT TO THE SINK. |
| | P1.1.2 SANITARY ISO AND FLOOR PLAN SHOW DISHWASHER |
| | DISCHARGING TO A FLOOR SINK. P2.1.1 PLUMBING FIXTURE |
| | CONNECTION SCHEDULE CALLS TO COMPLY WITH FBC PL 802.1.6 |
| | OR 802.1.7. PLEASE NOTE THAT IF DISCHARGING TO A FLOOR |
| | SINK PER 802.1.7, THAT THE FLOOR SINK SHALL NOT BE |
| | INSTALLED IN A CONCEALED PLACE BUT MUST HAVE READY |
| | ACCESS PER FBC PL 802.3. COMPLIANCE WITH FBC PL 802.1.6 |
| | ALLOWS FOR A SIMPLE UNDER THE COUNTER CONNECTION TO THE |
| | SINK WASTE SO LONG AS THE DISHWASHER IS ADJACENT TO THE |
| | SINK AS NOTED ON A1.1.1 AND THE REQUIREMENTS OF 802.1.6 |
| | ARE MET. PER WPB FBC 107.2.1, PLEASE CLARIFY WHICH |
| | INDIRECT WASTE METHOD IS TO BE USED ON BOTH THE |
| | SCHEDULE AND THE SANITARY PIPING DRAWINGS AS WELL AS |
| | THE ACTUAL LOCATION OF THE DISHWASHER. |
| | |
| | |
| | 2. ICEMAKER |
| | |
| | A. PER FBC PL 608.2 AND 608.3, PROVIDE A BACKFLOW |
| | PREVENTER IN THE WATER SUPPLY TO THE ICE MAKER AND |
| | INDICATE ON THE WATER RISER AND SPECIFY IN THE PLUMBING |
| | FIXTURE CONNECTION SCHEDULE. |
| | |
| | |
| | 3. RE: P2.1.1 |
| | |
| | A.GENERAL PLUMBING NOTES |
| | |
| | 1) DOMESTIC WATER PIPING NOTE 4; AMEND NOTE TO READ |
| | WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010 AND |
| | SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE |
| | UTILIZED AND WHERE SHOWN ON THE WATER RISER DIAGRAM. |
| | 2) DOMESTIC WATER PIPING NOTE 13 CALLS FOR A PRESSURE |
| | AND TEMPERATURE RELIEF VALVE FOR ALL WATER HEATERS |
| | (TANK-TYPE AND TANKLESS) AND AN EXPANSION TANK AS |
| | REQUIRED. PER WPB FBC107.2.1, CLARIFY WHETHER OR NOT |
| | ONE OR BOTH OF THESE ITEMS ARE REQUIRED FOR THE |
| | SCHEDULED TANKLESS WATER HEATER(S) AND IF THEY ARE |
| | REQUIRED THEN INCLUDE THEM IN THE ELECTRIC TANKLESS |
| | WATER HEATER DETAIL. ADDITIONALLY, IF THE RELIEF VALVE |
| | IS REQUIRED THEN PROVIDE FOR THE DISCHARGE OF SAID |
| | VALVE IN ACCORDANCE WITH FBC PL 504.6. |
| | 3) DO YOU REQUIRE AN EMERGENCY PAN FOR THE TANKLESS |
| | WATER HEATER AS STATED IN NOTE 12? IF SO THEN PROVIDE A |
| | DETAIL SHOWING COMPLIANCE WITH FBC PL 504.7.1 AND |
| | 504.7.2. IF NOT THEN REMOVE THE NOTE. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |